MN715P
Receiving and Installation
3-2
Control Installation
The control must be securely fastened to the mounting surface. Use the four
(4) mounting holes to fasten the control to the mounting surface or enclosure.
Shock Mounting
If the control will be subjected to levels of shock greater than 1G or vibration
greater than 0.5G at 10 to 60Hz, the control should be shock mounted.
Excessive vibration within the control can cause internal connections to
loosen and could lead to component failure or electrical shock hazard.
Electrical Installation
Interconnection wiring is required between the motor control, AC power
source, motor, host control and any operator interface stations. Use UL listed
closed loop connectors that are of an appropriate size for the wire gauge
being used. Connectors are to be installed using crimp tool specified by the
manufacturer of the connector. Only Class 1 wiring should be used.
System Grounding
Baldor controls are designed to be powered from standard three phase lines
that are electrically symmetrical with respect to ground. System grounding is
an important step in the overall installation to prevent problems.
Input Current Requirements
Table 3-2 Input Current Requirements for Stock Products
115VAC - 1
f
230VAC - 3
f
460VAC - 3
f
Catalog
Numbers
Input
Amps
Catalog
Numbers
Input
Amps
Catalog
Numbers
Input
Amps
ID15P1F33-ER
3.3
ID15P201-ER
4.8
ID15P401-ER
2.4
ID15P1F50-ER
5.0
ID15P201F5-ER
6.9
ID15P401F5-ER
3.5
ID15P1F75-ER
7.5
ID15P202-ER
7.8
ID15P402-ER
3.9
ID15P101-ER
10.0
ID15P203-ER
11.0
ID15P403-ER
5.5
ID15P405-ER
8.7
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com