Operation 4‐9
MN2408
Table 4‐17 Generator Protect Setpoints
Overload
Threshold for generator overload (in % of Nominal power)
Step: 1% of Nominal power; Range: 0 - 200%
Overload Wrn
Threshold for generator overload warning (in % of Nominal power)
Step: 1% of Nominal power; Range: 0 - 200%
Overload del
Delay for generator overload alarm. Step: 0.1s; Range: 0 - 60.0 s
Ishort
Shutdown occurs when short circuit limit Ishort limit is reached.
Step: 1 % of Nominal current; Range: 100 - 500 %
2Inom del
IDMT curve shape selection. 2Inom del is Reaction time of IDMT
protection for 200% overcurrent Igen = 2* Nominal current.
Step: 0,1 s; Range: 0,1 - 20 s
IDMT is “very inverse” generator over current protection. Reaction time is
not constant but depends on generator over current level according
following formula. Reaction time is limited up to 900 sec = 15 minutes.
IDMT protection is not active for Reaction time values longer than 15
minutes.
ReactionTime
+
2lnomdel * Nomincurrent
lgen
*
Nomincurrent
Curr unbal
Threshold for generator current asymmetry (unbalance).
Step: 1% of Nominal current; Range: 1 - 100% of Nominal current
Curr unbal del
Delay for generator current assymetry. Step: 0.1 s; Range: 0 - 60.0 s
Gen >V
Shutdown level for generator overvoltage. All three phases are checked.
Maximum out of three is used.
Step: 1% of Nominal voltage; Range: Gen >V Wrn -200%
Gen >V Wrn
Warning level for generator overvoltage. All three phases are checked.
Maximum out of three is used.
Step: 1% of Nominal voltage; Range: Gen <V Wrn - Gen >V
Gen <V Wrn
Warning level for generator under voltage. All three phases are checked.
Minimum out of three is used.
Step: 1% of Nominal voltage; Range: Gen <V - Gen >V Wrn
Gen <V
Shutdown level for generator under voltage. All three phases are checked.
Minimum out of three is used.
Step: 1% of Nominal voltage; Range: 0% - Gen <V Wrn
Gen V del
Delay for generator under voltage and over voltage alarm
Step: 0.1s; Range: 0 - 60 s
Volt unbal
Threshold for generator voltage unbalance alarm.
Step: 1% of Nominal voltage; Range: 0 - 100% of Nominal voltage
Volt unbal del
Delay for generator voltage unbalance alarm.
Step: 0.1s; Range: 0 - 60.0 s
Gen >f
Shutdown level for generator over frequency.
Step: 0.1% of Nominal frequency; Range: Gen > Wrn - 200.0%
Gen >f Wrn
Warning level for generator over frequency.
Step: 0.1% of Nominal frequency; Range: Gen <f Wrn - Gen >V
Gen <f
Shutdown level for generator under frequency.
Step: 0.1% of Nominal frequency; Range: 0.0 - Gen <f Wrn
Gen <f Wrn
Warning level for generator under frequency.
Step: 0.1% of Nominal frequency; Range: Gen <f - Gen >f Wrn
Gen f del
Delay for generator under frequency and over frequency alarm.
Step: 0.1s; Range: 0 - 60.0 s
Содержание GLC10
Страница 12: ...2 2 General Information MN2408...
Страница 24: ...2 14 General Information MN2408...
Страница 40: ...3 16 Receiving Installation MN2408...
Страница 58: ...4 18 Operation MN2408 Figure 4 15 Engine Controller Inputs Outputs...
Страница 70: ...4 30 Operation MN2408 Figure 4 16 Configuration Data Sheet j j j j j j j j j...
Страница 74: ...4 34 Operation MN2408...
Страница 88: ...A 10 Series GLC MN2408...
Страница 90: ...B 2 Series GLC MN2408 Figure B 11 Customer Interface Connection Diagram MEC20 MEC2...
Страница 91: ...Series GLC B 3 MN2408 Figure B 12 Customer Interface w o Breaker Power Connection Diagram...
Страница 92: ...B 4 Series GLC MN2408 Figure B 13 Single Phase w o Breaker Connection Diagram...
Страница 93: ...Series GLC B 5 MN2408 Figure B 14 Single Phase One Breaker Connection Diagram...
Страница 94: ...B 6 Series GLC MN2408 Figure B 15 Single Phase Two Breaker Connection Diagram...
Страница 95: ...Series GLC B 7 MN2408 Figure B 16 Single Phase Connection Diagram Wire 1 0 and Larger w Breaker...
Страница 96: ...B 8 Series GLC MN2408 Figure B 17 Single Phase Connection Diagram Wire 1 0 and Smaller w Breaker...
Страница 97: ...Series GLC B 9 MN2408 Figure B 18 Single Phase Connection Diagram Wire 1 0 and Smaller w o Breaker...
Страница 98: ...B 10 Series GLC MN2408 Figure B 19 Single Phase Connection Diagram Wire Larger than 1 0 w o Breaker...
Страница 99: ...Series GLC B 11 MN2408 Figure B 20 Three Phase Connection Diagram...
Страница 100: ...B 12 Series GLC MN2408 Figure B 21 Three Phase Connection Diagram with PMG...
Страница 101: ...Series GLC B 13 MN2408 Figure B 22 Three Phase Connection Diagram Wire 1 0 and larger...
Страница 102: ...B 14 Series GLC MN2408 Figure B 23 Three Phase Connection Diagram Wire Larger than 1 0 w Breaker...
Страница 103: ...Series GLC B 15 MN2408 Figure B 24 Three Phase Connection Diagram Wire 1 0 and Smaller w Breaker...
Страница 104: ...B 16 Series GLC MN2408 Figure B 25 Three Phase Connection Diagram Wire Larger than 1 0 w o Breaker...
Страница 105: ...Series GLC B 17 MN2408 Figure B 26 Three Phase Connection Diagram Wire 1 0 and Smaller w o Breaker...
Страница 106: ...B 18 Series GLC MN2408 Figure B 27 Control Box Connections with MEC20 Controller...
Страница 107: ...Series GLC B 19 MN2408 Figure B 28 Control Box Connections with MEC20 Controller Governor...
Страница 108: ...B 20 Series GLC MN2408 Figure B 29 Control Box Connections with MEC2 Controller...
Страница 109: ...Series GLC B 21 MN2408 Figure B 30 Engine Wiring Woodward 4 3L GM...
Страница 110: ...B 22 Series GLC MN2408 Figure B 31 Engine Wiring Woodward 5 7L GM...
Страница 111: ...Series GLC B 23 MN2408 Figure B 32 Engine Wiring Woodward 8 1L GM...
Страница 112: ...B 24 Series GLC MN2408...
Страница 113: ...Baldor District Offices...