background image

40985_F

12-08-11

22

Manufactured under one or more of these patents.  U.S. Patents: 5332944, 5361215, 5550753, 5559720, 5,883,459, 6253227, 6282370, 6590188, 6976052, 6965815, 7030343, 7,417,834 b2,
Canadian Patent: 2342614, Australian patent: 2373248 other patents both foreign and domestic applied for and pending.   All material copyright of Balboa Water Group.

Basic Installation and 
Confi guration Guidelines 

Use minimum 6AWG copper conductors only.

Torque fi eld connections between 21 and 23 in lbs.

Readily accessible disconnecting means to be provided at time of instal-
lation.

Permanently connected power supply.

Connect only to a circuit protected by a Class A Ground Fault Circuit Inter-
rupter (GFCI) or Residual Current Device (RCD) mounted at least 5’ (1.52M) 
from the inside walls of the spa/hot tub and in line of sight from the 
equipment compartment.

CSA enclosure: Type 2

Refer to Wiring Diagram inside the cover of the control enclosure.

Refer to Installation and Safety Instructions provided by the spa manufac-
turer.

Warning: 

People with infectious diseases should not use a spa or hot 

tub.

Warning: 

To avoid injury, exercise care when entering or exiting the spa 

or hot tub.

Warning: 

Do not use a spa or hot tub immediately following strenuous 

exercise.

Warning: 

Prolonged immersion in a spa or hot tub may be injurious to 

your health.

Warning: 

Maintain water chemistry in accordance with the Manufactur-

ers instructions.

Warning: 

The equipment and controls shall be located not less than 1.5 

meters horizontally from the spa or hot tub.

Warning! GFCI or RCD Protection.

The Owner should test and reset the GFCI or RCD on a 
regular basis to verify its function.

CSA Compliance/Conformité

Caution:

•  Test the ground fault circuit interrupter before each use of the spa.

•  Read the instruction manual.

•  Adequate drainage must be provided if the equipment is to be installed 
in a pit.

•  For use only within an enclosure rated CSA Enclosure 3.

•  Connect only to a circuit protected by a Class A ground fault circuit 
interrupter or residual current device.

•  To ensure continued protection against shock hazard, use only identical 
replacement parts when servicing.

•  Install a suitably rated suction guard to match the maximum fl ow rate 
marked.

Warning:

•  Water temperature in excess of 38°C may be injurious to your health.

•  Disconnect the electrical power before servicing.

Attention:

•  Toujours verifi er l’effi cacite du disjoncteur differentiel avant d’utiliser 
differentiel avant d’utiliser le bain.

•  Lire la notice technique.

•  Lorsque l’appareillage est installe dans une fosse, on doit assurer un 
drainage adequat.

•  Employer uniquement a l’interieur d’une cloture CSA Enclosure 3.

•  Connecter uniquement a un circuit protege par un disjoncteur differen-
tiel de Class A.

•  Afi n d’assurer une protection permanente contre le danger de shock 
electrique, lors de l’entretien employer seulement des pieces de rechange 
identiques.

•  Les prises d’aspiration doivent etre equipees de grilles convenant au 
debit maximal indique.

Avertissement:

•  Des temperatures de l’eau superieures a 38°C peuvent presenter un 
danger pour la sante.

•  Deconnecter du circuit d’alimentation electrique avante l’entretien.

Warning/Advertissement:

•  Disconnect the electric power before servicing. Keep access door closed.

•  Deconnecter du circuit d’alimentation electrique avant l’entretien. 
Garder la porte fermer.

Warning!  Qualifi ed Technician Required for Service and Installation

Warning! Shock Hazard! 
No User Serviceable Parts.

Do not attempt service of this control system. Contact your 
dealer or service  organization for assistance. Follow all 
owner’s manual power connection  instructions. Installation 
must be performed by a licensed electrician and all ground-
ing connections must be properly installed.

Содержание TP800 series

Страница 1: ... both foreign and domestic applied for and pending All material copyright of Balboa Water Group TP800 and TP900 Series Control Panels Balboa Water Group Colossus Series User Interface and Programming Reference System Model BP2500 2600 Software Version 5 0 and later Panel Model TP900 Series TP800 Series Software Version 2 0 or later 1 9 or later Set 104 F 8 32 PM Ozone Filter 1 Spa Shortcuts Settin...

Страница 2: ... accessed from this screen The actual water temperature can be seen in large text and the desired or Set Temperature can be selected and adjusted Time of day Ozone operation and Filter Operation status is available along with other messages and alerts High Temperature Range vs Low Temperature Range is indicated in the upper right corner The Jets Icon in the center will spin on a TP900 if any pump ...

Страница 3: ...Set Temperature Press the Left Arrow button to change the Set Temperature number to white The Set Temperature can then be adjusted with the up and down buttons Pressing the Select button or the Right Arrow button will save the new set temperature On the right side of the screen the menu selections can be selected with the Up and Down Buttons Use the Select Button to choose an item Selecting one of...

Страница 4: ...der the icon changes to white Once a device is selected it can be controlled using the center Select Button Some devices like pumps may have more than one ON state so the icon will change to reflect the state that the equipment is in Below are some examples of 2 speed Pump indicators Jets High Jets Low Jets Off If the Spa has a Circ Pump a Circ Pump Icon will appear to indicate its activity but ou...

Страница 5: ...ice while on the Shortcuts Screen if the device is one of the 4 functions available Settings Back Temp Range Heat Mode Time of Day Filter Cycles Light Cycle Invert Panel Lock High Ready Normal Press and Hold If an Up or Down button is pressed and held when an item in a Menu List is highlighted the list can be scrolled quickly from top to bottom The scroll bar on the right side of the screen indica...

Страница 6: ...nt temperature until the heater pump has been running for a minute or two While Pump 1 High can be turned on and off Pump 1 Low will run until set temperature is reached or 1 hour has passed Circulation Mode See Page 8 under Pumps for other circulation modes If the spa is configured for 24HR circulation the heater pump generally runs continuously Since the heater pump is always running the spa wil...

Страница 7: ...ton Priming the Pumps As soon as the Priming Mode screeen appears on the panel select the Jets 1 button once to start Pump 1 in low speed and then again to switch to high speed Also select the other pumps to turn them on The pumps should be running in high speed to facilitate priming If the pumps have not primed after 2 minutes and water is not flowing from the jets in the spa do not allow the pum...

Страница 8: ...eze conditions or when another pump is on The specific Circulation Mode that is used has been determined by the Manufacturer and cannot be changed in the field Other device options may be available like Blower Light Mist etc Filtration and Ozone On non circ systems Pump 1 low and the ozone generator will run during filtration On circ systems the ozone will gener ally run with the circ pump but can...

Страница 9: ...f Day screen simply navigate right and left to select the Hour Minutes AM PM and 12 24 Hour segments Use the Up and Down Buttons to make changes Saving Settings The Time of Day screen is a simple editable screen that illustrates a feature of the control that applies to all other editable screens as well When changes are made the icon to go Back changes to Save and a new icon for Cancel appears und...

Страница 10: ...Cycle 1 by navigating to the right It is possible to overlap Filter Cycle 1 and Filter Cycle 2 which will shorten overall filtration by the overlap amount Circulation Pump Modes Some spas may be manufactured with Circ Pump settings that allow programming filtration cycle duration Some circ Modes are pre programmed to operate 24 hours a day and are not programmable Refer to the spa manufacturer s d...

Страница 11: ... default The settings can be edited the same way that Filter Cycles are edited see page 10 Specific Buttons for Specific Devices If the panel has dedicated function buttons TP800 or the spa has an Auxiliary Panel s installed pressing those buttons will activate the device indicated for that button These dedicated buttons will operate just like the Spa Screen buttons see page 4 and the equipment wi...

Страница 12: ...r both Panel Lock and Settings Lock The control can be restricted to prevent unwanted use or temperature adjustments Locking the Panel prevents the controller from being used but all automatic functions are still active Locking the Settings allows Jets and other features to be used but the Set Temperature and other programmed settings cannot be adjusted Settings Lock allows access to a reduced sel...

Страница 13: ...Mode Utilities The Utilities Menu contains the following A B Temps When this is set to On the temperature display will alternate to display temperature from Sensor A and Sensor B in the heater Demo Mode Demo Mode is not always enabled so it may not appear This is designed to operate several devices in a sequence in order to demonstrate the various features of a particular hot tub Fault Log The Fau...

Страница 14: ...eminders Turn the reminder messages like Clean Filter On or Off Cleanup Cleanup Cycle Duration is not always enabled so it may not appear When it is available set the length of time Pump 1 will run after each use 0 4 hours are available Dolphin II and Dolphin III Applies to RF Dolphin only When set to 0 no addressing is used Use this setting for a Dolphin II or Dolphin III which is factory set for...

Страница 15: ...stem Model Displays the Model Number of the System Current Setup Displays the currently selected Configuration Setup Number Configuration Signature Displays the checksum for the system configuration file Heater Voltage Feature not used on CE rated systems Displays the operating voltage configured for the heater Heater Wattage as Configured in Software CE Systems Only Displays a heater kilowatt rat...

Страница 16: ...ut off until a service person can correct the problem Forcing the GFCI Trip Test North America Only The installer can cause the GFCI Trip Test to occur sooner by initiating it using the above menu The GFCI should trip within several seconds and the spa should shut down If it does not shut down the power and manually verify that a GFCI breaker is installed and that the circuit and spa are wired cor...

Страница 17: ...message can be selected by navigating to it at pressing the Select button The water is too hot M029 The system has detected a spa water temp of 110 F 43 3 C or more and spa functions are disabled System will auto reset when the spa water temp is below 108 F 42 2 C Check for extended pump operation or high ambient temp This message can be reset from the topside panel Possible freezing condition A p...

Страница 18: ...in heater start up The heater may be dry M028 Possible dry heater or not enough water in the heater to start it The spa is shut down for 15 min Press any button to reset the heater start up See Flow Related Checks below The heater is dry M027 There is not enough water in the heater to start it The spa is shut down After the problem has been resolved you must clear the message to restart heater sta...

Страница 19: ...or 3 F Call for Service Sensors are out of sync Call for service M026 The temperature sensors ARE out of sync The fault above has been established for at least 1 hour Call for Service Sensor A Fault Senor B Fault Sensor A M031 Sensor B M032 A temperature sensor or sensor circuit has failed Call for Service Communications error The control panel is not receiving communication from the System Call f...

Страница 20: ... organization The GFCI test failed System Could Not Test the GFCI M036 North America Only May indicate an unsafe installation Contact your dealer or service organization Hot fault M035 A Pump Appears to have been Stuck ON when spa was last powered POWER DOWN THE SPA DO NOT ENTER THE WATER Contact your dealer or service organization A pump may be stuck on M034 Water may be overheated POWER DOWN THE...

Страница 21: ...I or RCD associated with the hot tub installation A GFCI or RCD will have a TEST and RESET button on it that allows a user to verify proper function General maintenance helps Reminder Messages can be suppressed by using the Preferences Menu See Page 14 Reminder Messages can be chosen individually by the Manufacturer They may be disabled entirely or there may be a limited number of reminders on a s...

Страница 22: ... instruction manual Adequate drainage must be provided if the equipment is to be installed in a pit For use only within an enclosure rated CSA Enclosure 3 Connect only to a circuit protected by a Class A ground fault circuit interrupter or residual current device To ensure continued protection against shock hazard use only identical replacement parts when servicing Install a suitably rated suction...

Отзывы: