Masoneilan 21009 Series Cage Guided Globe Valve Instruction Manual | 2
Copyright 2021 Baker Hughes Company. All rights reserved.
2nd
4th
3rd
2nd
1st
1st
5th
6th
Body
Size
10
51 - Cylinder Double acting
52 - Spring Cylinder
Air to Open
53 - Spring Cylinder
Air to Close
87 - Spring Diaphragm
Air to Close
88 - Spring Diaphragm
Air to Open
Actuator Type
Plug
Type
0. Undefined
1. Contoured
Flow
Characteristics
0. Undefined
1. Linear
2. Equal Percentage
3. Modified Percentage
Optional
Configuration
EB. Extension Bonnet
Seat
Type
9. Metal and
Retainer
Guide
Figure 1 - Numbering System
1. Introduction
The following instructions should be thoroughly reviewed
and understood prior to installing, operating or performing
maintenance on this equipment .Throughout the text, safety
and/or caution notes will appear and must be strictly adhered to,
otherwise, serious injury or equipment malfunction could result .
Baker Hughes has a highly skilled After Sales Department
available for start-up, maintenance and repair of our valves and
component parts.
Arrangements for this service can be made through your
local Masoneilan representative or sales department. When
performing maintenance use only Masoneilan replacement
parts. Parts are obtainable through your local representative or
spare parts department. When ordering parts, always include
model and Serial Number of the unit being repaired.
2. General
These installation and maintenance instructions apply to all
sizes and ratings of the 21009 Series control valves regardless
of the type of trim used.
21009 Series single ported Cage guided control valves are
designed with built in versatility making them well-suited to
handle a wide variety of process applications.
Standard construction offers a contoured plug (21109 Series)
with a quick change seat ring. The heavy Cage plug guiding
provides maximum support to ensure plug stability.
A series of reduced area trim is available to provide wide flow
range capabilities in all valve sizes.
Tight Shutoff Class IV leakage is standard. Optional constructions
meet IEC 534-4 and ANSI/FCI 70.2 Class V requirements.
Recommended spare parts required for maintenance are listed
in the Parts Reference table on page 10. The model number,
size, rating and serial number of the valve are shown on the
identification tag located on the actuator. Refer to Figure 1 for
the 21009 series numbering system.
3. Unpacking
Care must be exercised when unpacking the valve to prevent
damage to the accessories and component parts. Should
any problems arise, contact your local GE’s Masoneilan
representative or sales department.
4. Installation
4.1
Before installing the valve in the line, clean piping and
valve of all foreign material such as welding chips, scale,
oil, grease or dirt. Gasket surfaces should be thoroughly
cleaned to ensure leak-proof joints.
4.2
To allow for in-line inspection, maintenance or removal of
the valve without service interruption, provide a manually
operated stop valve on each side of the 21009 Series valve
with a manually operated throttling valve mounted in the
by-pass line (See Figure 2).
4.3
The valve must be installed so that the controlled substance
will flow through the valve in the direction indicated by the
flow arrow located on the body.
• With contoured plug : flow-to-open
4.4
For heat-insulated installation, do not insulate the valve
bonnet. Take necessary protective measures relate to
personal safety.