Message on LCD /
ValVue (English)
Description
Device Action
(Warning message only or
Failsafe position)
Probable Cause
Recommended Action
V
OLTAGE
HART
®
L
OW
HART voltage below threshold
Warning message
Internal voltage may have
changed
Clear the condition using
ValVue software or HART
host.
If the failure persists, replace
the device.
V
OLTAGE
HART
®
H
IGH HART voltage above threshold
Warning message
Internal voltage may have
changed
Clear the condition using
ValVue software or HART
host.
If the failure persists, replace
the device.
V
OLTAGE
CORE
L
OW
Core (CPU) voltage below threshold
Warning message
Internal voltage may have
changed
Clear the condition using
ValVue software or HART
host.
If the failure persists, replace
the device.
V
OLTAGE
CORE
H
IGH
Core (CPU) voltage above threshold
Warning message
Internal voltage may have
changed
Clear the condition using
ValVue software or HART
host.
If the failure persists, replace
the device.
LEVEL OUTPUT
SATUTARED
Normal level output is clamped from
below at 3.8 mA or from above at 20.5 mA
Warning message
Level variable is saturated and
outside the normao operating
range (3.8 to 20.5mA)
Reduce level measurement
or checl configuration and
calibration.
L
E
V
E
L RANGE
Specific Gravity recalculated range
exceeded the linearization table limits
Warning message
Specific Gravity value(s) is(are)
incorrect or bad calibration
Check Specific Gravity data
or instrument calibration
L
E
V
E
L CLAMP
Internal position or adjusted position is
outside the range of +/- 200%
Warning message
Bad calibration or mechanical
hardware adjustment
Check displacer and torque
tube S/A characteristics.
Redo calibration.
SG L
E
V
E
L MAX
Absolute value of Specific Gravity
recalculated range is too small
Warning message
Specific Gravity value(s) is(are)
incorrect
Check Specific Gravity data
SENSOR
SUPPLY
V
OLTAGE
Sensor supply voltage was outside sensor
specification
Failsafe position
Lack of supply power or circuit
board component failure
Clear the condition using
ValVue software or HART
host.
Check supply power.
If the failure persists, replace
the device.
SENS
O
R OFF
Sensor turned off because of too low
analog current during 5 seconds
Warning message
Lack of supply power or circuit
board component failure
Clear the condition using
ValVue software or HART
host.
Check supply power.
If the failure persists, replace
the device.
LEVEL FAIL
URE, OUT
OF RANGE
Level value is critically out of range (above
105% or below -5%) for a predefined time
(10 to 1000 seconds).
Failsafe position
- Fail Low only for a SIL device
Bad calibration or mechanical
hardware adjustment
Check displacer and torque
tube S/A characteristics.
Redo calibration.
SENSOR OUT OF
RANGE
(SIL)
Level value is critically out of normal range
which includes limits of full linearization
table range
Failsafe position (Fail Low)
Bad calibration or mechanical
hardware adjustment
Check displacer and torque
tube S/A characteristics.
Redo calibration.
4-20
LOOP OUTPUT
FAIL
URE (SIL)
Mismatch between commanded and read
4-20 mA loop output (lower than 0.64 mA)
Failsafe position (Fail Low)
Resistance change of external
loop may have changed
Perform an instrument reset
or switch off then switch on.
If the failure persists, replace
the device.
Содержание Masoneilan 12400 Series
Страница 46: ...44 BHGE 2017 Baker Hughes a GE company All rights reserved...
Страница 62: ...60 BHGE 2017 Baker Hughes a GE company All rights reserved APPENDICES...
Страница 68: ...66 BHGE 2017 Baker Hughes a GE company All rights reserved APPENDIX C see following pages...
Страница 72: ...70 BHGE 2017 Baker Hughes a GE company All rights reserved APPENDIX D see following pages...