REPAIR/REPLACEMENT PROCEDURES
FUSE REPLACEMENT PROCEDURES
4 - 2
I-E96-409A
®
10. Install the front cover on the replacement ICS module.
11. Apply power to the PCU containing the replacement ICS
module.
FUSE REPLACEMENT PROCEDURES
If the fuse is faulty, replace it with a new one. To replace a fuse:
1. Turn off power to the PCU containing the ICS module.
2. Remove the front cover of the ICS module.
3. Pull the ICS module out far enough to gain access to the
fuse clip F1.
4. Remove the faulty fuse.
5. Install the replacement fuse into fuse clip F1.
6. Insert the module until it locks securely into place.
7. Install the front cover of the module.
8. Apply power to the PCU containing the ICS module.
CAUTION
It is strongly recommended that
all
power (cabinet, I/O, etc.) be
turned off before doing any termination module wiring. Failure
to do so could result in equipment damage. Do not apply
power until all wire connections are verified.
ATTENTION
Il est fortement recommandé que
toutes
les alimentations
(armoire, E/S, etc.) soient coupées avant d'effectuer quelque
raccord que ce soit sur un carte de raccordement. Un manque-
ment à ces instructions pourrait causer des dommage à
l'équipement. Ne pas rebrancher les alimentations avant
d'avoir vérìfié tous les raccordements.