INSTALLATION
SETUP/PHYSICAL INSTALLATION
I-E96-409A
2 - 5
Cable Installation
Remove the front cover of the termination module before trying
to install cables. Use the following descriptions when installing
cables.
NKTU02, NKTU12 and NKTM01
This cable connects the ICS module to a master/slave module.
To install the cable:
1. Pull the master/slave module out several inches from the
module mounting unit (MMU) backplane.
Table 2-3. NICS01 Cable Applications
Nomenclature/
Description
Application
Connections
Max. Length
Meters (Feet)
NKTU02 PVC Jacket Ter-
mination Cable
Connects ICS module to
master slave module
P1 of ICS module to P3 of
master/slave module
61
(200)
NKTU12 non-PVC Jacket
Termination Cable
NKTM01 Ribbon
Cable
Connects ICS module to
master/slave module
P1 of ICS module to P3 of
master/slave module
30
(100)
NKTD02 PVC Jacket Ter-
mination Cable
Connects ICS module to a
station
J2 of ICS module to P1 of the
station
183
(600)
NKTD12 non-PVC Jacket
Termination Cable
Serial Link Wire
Enables serial link from ICS
to NICS01, NIMF01, NIMP01/
02, or NIRL03
Terminal strip of ICS module
to other termination module
strip.
N/A
6634408_2 Ribbon
Cable
Connects ICS module to the
NIDS01 module
J1 of ICS module to J1 of the
NIDS01 module.
N/A
Standard 14 to 22 AWG
Wire
Connects field and power wir-
ing to ICS module
Field or power source to the
ICS terminal strip.
N/A
CAUTION
Remove modules (slave, master or termination) from their
assigned slots before installing a cable to that slot. Also,
remove stations from their housing before installing a cable to
that housing. Failure to do so could result in damage to the
module or station.
ATTENTION
Retirer les modules (asservi, maître ou carte de raccordement)
de leur position assignée avant d'installer un câble à cette
position. Egalement, retirer les postes de commande de leur
boîtier avant d'installer un câble dans ce boîtier. Des dom-
mages au module ou au poste pourraient résulter d'un man-
quement à cette procédure.