INTRODUCTION
SPECIFICATIONS
I-E96-409A
1 - 3
SPECIFICATIONS
Refer to Table
for the specifications of the NICS01 Termi-
nation Module.
DCS
Digital control station. Provides monitoring and allows manipulation of a single process
control loop and communicates with the MFP module. It has front panel LED bar graphs
that display set point, process variable and control output values.
Digital
A discretely variable signal usually having only two states,
on or off.
DIS
Digital indicator station. A panel mounted device that displays information from control-
ler, multi-function controller and multi-function processor modules.
MFC
Multi-function controller module. A multiple-loop controller with data acquisition and infor-
mation processing capabilities.
MFP
Multi-function processor module. A multiple-loop controller with data acquisition and
information processing capabilities.
MMU
Module mounting unit. A card cage that provides electrical and communication support
for INFI 90
®
/Network 90
®
modules.
QRC
Quick response controller.
QRS
Quick response slave.
Serial Link
Wire
Two insulated 22 gauge wires twisted together. Each wire of the twisted pair consists of
seven strands of 30 gauge wire. This twisted pair is shielded with a 36 gauge woven
shield drain wire. Bailey raw material P/N R2041-0397.
SAC
Analog control station. Provides monitoring and allows manipulation of a single process
control loop and communicates with the MFC, MFP and COM modules. It has front panel
LED bar graphs that display set point, process variable and control output values.
TM
Termination module. Provides input/output connection between plant equipment and
INFI 90/Network 90 modules.
TMU
Termination mounting unit. A card cage that provides housing for INFI 90/
Network 90 termination modules.
Table 1-1. Glossary of Terms and Abbreviations
(continued)
Term
Definition
® Registered trademarks of Elsag Bailey Process Automation.
Table 1-2. Specifications
Physical Attribute/Function
Capabilities
Surge Protection
Meets IEEE-472-1974 surge withstand capability test.
1
Certification
CSA certified for use as process control equipment in an ordinary (non-
hazardous) location.
Environmental
Ambient Temperature
Relative Humidity
Air Quality
0
°
to 70
°
C (32
°
to 158
°
F).
0% to 95% up to 55
°
C (131
°
F) (noncondensing).
0% to 45% up to 70
°
C (158
°
F) (noncondensing).
Noncorrosive.
Mounting
Occupies one slot in a standard INFI 90 termination mounting unit.
NOTE:
1. Does not meet test when the NKTM01 cable is used.