MODULAR POWER SYSTEM SIZING TABLES
INTRODUCTION
D - 2
I-E96-508C
®
Use Table
to size systems that use both the IEPDS01 and
IEPDS02 and IEPDF01 and IEPDF02 modules. Table
lists
two values (Q1 and QF) for the 5 VDC and 24 VDC (A and B)
current requirements. The value of Q1 indicates how many
PDS modules are needed to meet system requirements. The
value of QF indicates how many PDF modules are needed to
meet system requirements.
Table D-2. Q1 and QF for Systems Using IEPDS01/02 and IEPDF01/02 Modules
A
B
0
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
0
Q1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
QF
0
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
5
Q1
1
1
1
1
1
1
1
2
2
2
2
2
2
2
2
2
QF
0
0
1
1
2
2
3
3
4
4
5
5
6
6
7
7
10
Q1
1
1
1
2
2
2
2
2
2
2
2
2
2
3
3
3
QF
0
0
1
0
1
2
2
3
4
4
5
6
6
5
6
6
15
Q1
2
2
2
2
2
2
2
3
3
3
3
3
3
3
3
3
QF
0
0
0
1
2
2
3
2
3
3
4
5
5
6
7
7
20
Q1
2
2
2
2
2
3
3
3
3
3
3
3
3
4
4
4
QF
0
0
0
1
2
1
2
3
3
4
5
6
6
5
6
6
25
Q1
3
3
3
3
3
3
3
3
3
4
4
4
4
4
4
4
QF
0
0
0
0
1
2
3
3
4
3
4
4
5
6
7
7
30
Q1
3
3
3
3
3
3
3
4
4
4
4
4
4
4
5
5
QF
0
0
0
0
1
2
3
2
3
4
4
5
6
7
5
6
35
Q1
4
4
4
4
4
4
4
4
4
4
4
5
5
5
5
5
QF
0
0
0
0
0
1
2
3
4
4
5
4
5
5
6
7
40
Q1
4
4
4
4
4
4
4
4
4
5
5
5
5
5
5
5
QF
0
0
0
0
0
1
2
3
4
3
4
5
5
6
7
8
45
Q1
5
5
5
5
5
5
5
5
5
5
5
5
5
6
6
6
QF
0
0
0
0
0
0
1
2
3
4
5
5
6
5
6
6
50
Q1
5
5
5
5
5
5
5
5
5
5
5
6
6
6
6
6
QF
0
0
0
0
0
0
1
2
3
4
5
4
5
6
6
7
55
Q1
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
7
QF
0
0
0
0
0
0
0
1
2
3
4
5
6
6
7
6
60
Q1
6
6
6
6
6
6
6
6
6
6
6
6
6
7
7
7
QF
0
0
0
0
0
0
0
1
2
3
4
5
6
5
6
7
65
Q1
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
QF
0
0
0
0
0
0
0
0
1
2
3
4
5
6
7
7
70
Q1
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
8
QF
0
0
0
0
0
0
0
0
1
2
3
4
5
6
7
6
75
Q1
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
QF
0
0
0
0
0
0
0
0
0
1
2
3
4
5
6
7