INTRODUCTION
REFERENCE DOCUMENTS
I-E96-508C
1 - 5
REFERENCE DOCUMENTS
Table
lists other Bailey documents containing information
relevant to the DC modular power system.
SPECIFICATIONS
Table
lists DC modular power system specifications.
24 VDC input field power module
48 VDC input field power module
IEPDF01
IEPDF02
24 VDC input system power module
48 VDC input system power module
IEPDS01
IEPDS02
DC power entry panel with redundant DC feed and
circuit breakers
IEPEP04
Power mounting unit
Rear mount
Front mount
IEPMU01
IEPMU02
NOTE: The DC transfer module and bus monitor module have part numbers (refer to Table
Table 1-2. Nomenclature
(continued)
Description
Nomenclature
Table 1-3. Reference Documents
Number
Document Title
I-E96-500
Site Planning and Preparation
Table 1-4. Specifications
Property
Characteristic/Value
IEPDS01/02, IEPDF01/02 Power Modules
Module input requirements
Module outputs
Module
Voltage (VDC)
Current (A)
Max
Power (W)
Nom
Min
Nom
Max
IEPDF01
21
24
30
6.5
102
IEPDF02
42
48
60
3.25
102
IEPDS01
21
24
30
7.6
117
IEPDS02
42
48
60
3.8
117
NOTE: Inrush current increases from 0 A to steady state in 3 seconds typically.
Module
Voltage
(VDC)
Current
(A)
Power
(W)
Tolerance
(%)
IEPDF01/02
25.5
4.0
102.0
+6/-0
IEPDS01/02
5.1
10.0
51.0
±
3.0
-15.0
0.5
7.5
±
2.3
+15.0
0.5
7.5
±
2.3
25.5
4.0
102.0
+6/-0
NOTE: Total 5 VDC and 24 VDC power output per module should not exceed 102 watts.