INSIM01 SERIAL INTERFACE MODULE CONFIGURATION
INTRODUCTION
I-E96-417A
B - 3
Jumpers JP3 through JP6 set the RS-232-C handshaking sig-
nals for the diagnostic terminal and computer. Table B-5 con-
tains the settings for jumpers JP3 through JP6. Refer to the
INPCI01 Plant Loop to Computer Interface
instruction man-
ual for details on required handshaking signals. Figure
shows the jumper settings for the available communication
baud rates of the RS-232-C ports on the SIM module. Short the
appropriate set of pins by placing a jumper over them to select
a particular baud rate.
Jumpers JP11 and JP12 set the clear to send (CTS), data set
ready (DSR), and data carrier detect (DCD) handshaking lines.
These lines are not required by the SIM module. Shorting pins
2 and 3 by placing a jumper across them ties these signals to
+12 VDC.
Table B-4. Handshaking Signal Options
Bypass Options
Jumper Settings
JP3
JP4
JP5
JP6
Not allowed
1 to 2
Diagnostic terminal not
required to provide RTS
2 to 3
Enable DTR from diagnostic
terminal to SIM module
1 to 2
Disable DTR from diagnostic
terminal to SIM module
1 to 2
Not allowed
1 to 2
Computer not required to
provide RTS
2 to 3
Enable DTR from computer to
SIM module
1 to 2
Disable DTR from computer
to SIM module
2 to 3
NOTE: Short pins by inserting a jumper over them to enable option.
Figure B-2. Jumper Settings for
Communication Baud Rates
19,200
9,600
2,400
1,200
300
T00402A
JP9 AND JP10