IMHSS02 HYDRAULIC SERVO SLAVE MODULE CONFIGURATION
INTRODUCTION
H - 2
I-E96-410A
®
Table H-1. IMHSS02 Switch S1 (Address Examples)
Address
Example
Switch Position
(Binary Value)
1
1
(128)
2
1
(64)
3
(32)
4
(16)
5
(8)
6
(4)
7
(2)
8
(1)
0
0
0
0
0
0
0
0
0
15
0
0
0
0
1
1
1
1
30
0
0
0
1
1
1
1
0
45
0
0
1
0
1
1
0
1
63
0
0
1
1
1
1
1
1
NOTES: 0 = CLOSED or ON, 1 = OPEN or OFF.
1. Switch positions 1 and 2 must remain CLOSED.
Table H-2. IMHSS02 Switch S2 (Controller Gain)
Switch Positions
Function
1
2
3
4
5
6
7
8
0
1
1
1
1
1
1
1
Amplifier gain of 20.50
1
0
1
1
1
1
1
1
Amplifier gain of 18.25
1
1
0
1
1
1
1
1
Amplifier gain of 15.05
1
1
1
0
1
1
1
1
Amplifier gain of 13.10
1
1
1
1
0
1
1
1
Amplifier gain of 10.00
1
1
1
1
1
0
1
1
Amplifier gain of 5.00
1
1
1
1
1
1
0
1
Amplifier gain of 2.01
1
1
1
1
1
1
1
0
Amplifier gain of 1.10
NOTE:0 = CLOSED or ON, 1 = OPEN or OFF. Close only one switch at a time.
Table H-3. IMHSS02 Switch S3
(Oscillator Frequency)
Switch Position
Function
1
2
1
0
Oscillator frequency of 200 Hz
0
1
Oscillator frequency of 300 Hz
NOTE: 0 = CLOSED or ON, 1 = OPEN or OFF. Do not leave both