INTRODUCTION
NOMENCLATURE
1 - 4
I-E96-410A
®
NOMENCLATURE
is a list of related hardware.
SPECIFICATIONS
Refer to Table
for the specifications of the IDI termination module .
Table 1-3. Nomenclature
Nomenclature
Hardware/Description
NIDI01
Digital input termination module.
NKTU02
Termination module cable (PVC).
NKTU12
Termination module cable (non-PVC).
NKTM01
Termination module cable (ribbon).
NTMU01
Termination mounting unit, rear mounting.
NTMU02
Termination mounting unit, front mounting.
258436A1
Cable retaining kit used when at least one round cable is
connected to the termination mounting unit.
Table 1-4. Specifications
Property
Characteristic/Value
Power Requirements
+24 VDC from 24 VDC bus bar of the termination mounting unit (when used
with IMASO01, IMDSM04 and IMDSM05 modules).
Mounting
Occupies one slot in a standard INFI 90 termination mounting unit.
Surge Protection
Meets IEEE-472-1974 Surge Withstand Capability Test
1
.
Inputs and Outputs
Module
Qty
Inputs
Outputs
Analog
Digital
Analog
Digital
IMASO01
10
1-5 VDC and
4-20 mA
IMDSI02
16
120 VAC,
125 VDC
and 24 VDC
IMDSM04
8
50 mVp-p -
10 Vp-p,
0-6 VDC,
and 0-27
VDC
IMDSM05
up to
16
24 VDC
up to
16
24 VDC
IMDSO01/
02/03
8
24-240 VAC,
4-60 VDC,
and 5-160
VDC
IMDSO04
16
24 VDC
IMFCS01
1
0.3 Vp-p -
120 VAC