IMDSM05 DIGITAL I/O SLAVE MODULE CONFIGURATION
INTRODUCTION
D - 2
I-E96-410A
®
Table D-1. IMDSM05 Switch S1 (Default Output Values)
Switch
Position
1 - 8
Function
1
An output signal will be sent to the Group A output point
corresponding to the switch position number during
default conditions.
0
No output signal will be sent during default.
NOTE: 0 = CLOSED or ON, 1 = OPEN or OFF.
Table D-2. IMDSM05 Switch S2 (Default Output Values)
Switch
Position
1 - 8
Function
1
An output signal will be sent to the Group B output point
corresponding to the switch position number during
default conditions.
0
No output signal will be sent during default.
NOTE: 0 = CLOSED or ON, 1 = OPEN or OFF.
Table D-3. IMDSM05 Switch S3 (I/O Configuration)
Switch Position
Function
1
2
3
4
1
Set Group A I/O points to outputs.
0
Set Group A I/O points to inputs.
1
Set Group B I/O points to outputs.
0
Set Group B I/O points to inputs.
1
Module is an interface between a master module
and a digital logic station (switch positions 1 and 2
must be set to 1, switch position 4 must be set to 0,
and switch position 8 of switch S2 must be set to 0).
0
Module is an I/O interface between a master mod-
ule and field devices.
1
All outputs hold on master module failure.
0
All outputs go to default value on master module
failure.
NOTE: 0 = CLOSED or ON, 1 = OPEN or OFF.