INSTALLATION
SETUP/PHYSICAL INSTALLATION
2 - 6
I-E96-410A
®
NOTE:
Proper polarity of all signals must be maintained.
To connect field and power wiring:
1. Insure the IDI module is pulled out far enough to gain
access to the terminal strip.
2. Feed the field wiring into the terminal strip area and con-
nect them to the appropriate terminals.
3. If 24 VDC power is required, connect an 18 AWG wire from
the 24 VDC bus of the termination mounting unit to the 24
VDC terminal of the IDI module.
4. If 24 VDC power is required, connect an 18 AWG wire from
the common bus of the termination mounting unit to the com-
mon terminal of the IDI module.
5. Insert the IDI module until it locks securely into place.
6. Replace (snap on) the front cover.
The IDI module is ready for operation if:
1. The jumpers are configured for the type of master or slave
module used.
WARNING
If input or output circuits are a shock hazard after disconnect-
ing system power at the power entry panel, then the door of the
cabinet containing these externally powered circuits must be
marked with a warning stating that multiple power sources
exist.
AVERTISSEMENT
Si des circuits d'entree ou de sortie sont alimentes a partir de
sources extrenes, ils presentent un risque de choc electrique
meme lorsque l'alimentation du systeme est debranchee du
panneau d'entree l'alimentation. Le cas echeant, un avertisse-
ment signalant la presence de sources d'alimentation multiples
doit entre appose sur la porte de l'armoire.
CAUTION
It is strongly recommended that all power (cabinet, I/O, etc.) be
turned off before doing any termination module wiring. Failure
to do so could result in equipment damage. Do not apply
power until all connections are verified.
ATTENTION
Il est fortement recommand, que toutes les alimentations (arm-
oire, E/S, etc.) soient coupées avant d'effectuer quelque rac-
cord que ce soit sur un carte de raccordement. Un
manquement à ces instructions pourrait causer des dommage
à l'équipement. Ne pas rebrancher les alimentations avant
d'avoir vérifié tous les raccordements.