INSTALLATION

SETUP/PHYSICAL INSTALLATION

2 - 6

  

I-E96-410A

®

NOTE: 

Proper polarity of all signals must be maintained.

To connect field and power wiring:

1. Insure the IDI module is pulled out far enough to gain
access to the terminal strip.

2. Feed the field wiring into the terminal strip area and con-
nect them to the appropriate terminals.

3. If 24 VDC power is required, connect an 18 AWG wire from
the 24 VDC bus of the termination mounting unit to the 24
VDC terminal of the IDI module.

4. If 24 VDC power is required, connect an 18 AWG wire from
the common bus of the termination mounting unit to the com-
mon terminal of the IDI module.

5. Insert the IDI module until it locks securely into place.

6. Replace (snap on) the front cover.

The IDI module is ready for operation if:

1. The jumpers are configured for the type of master or slave
module used.

WARNING

If input or output circuits are a shock hazard after disconnect-
ing system power at the power entry panel, then the door of the
cabinet containing these externally powered circuits must be
marked with a warning stating that multiple power sources
exist.

AVERTISSEMENT

Si des circuits d'entree ou de sortie sont alimentes a partir de
sources extrenes, ils presentent un risque de choc electrique
meme lorsque l'alimentation du systeme est debranchee du
panneau d'entree l'alimentation. Le cas echeant, un avertisse-
ment signalant la presence de sources d'alimentation multiples
doit entre appose sur la porte de l'armoire.

CAUTION

It is strongly recommended that all power (cabinet, I/O, etc.) be
turned off before doing any termination module wiring. Failure
to do so could result in equipment damage. Do not apply
power until all connections are verified.

ATTENTION

Il est fortement recommand, que toutes les alimentations (arm-
oire, E/S, etc.) soient coupées avant d'effectuer quelque rac-
cord que ce soit sur un carte de raccordement. Un
manquement à ces instructions pourrait causer des dommage
à l'équipement. Ne pas rebrancher les alimentations avant
d'avoir vérifié tous les raccordements.

Содержание infi 90 NIDI01

Страница 1: ...Process Control and Automation Solutions from Elsag Bailey Group E96 410 Digital Input Termination Module NIDI01...

Страница 2: ...UIPEMENTS LECTRONIQUES SONT SENSIBLES AUX PERTURBATIONS PAR FR QUENCE RADIO DES PR CAUTIONS DEVRONT TRE PRISES LORS DE L UTILISATION DU MAT RIEL DE COMMUNICATION PORTATIF LA PRUDENCE EXIGE QUE LES PR...

Страница 3: ...ut Module IMDSI02 Digital Slave Input Module IMDSM04 Pulse Input Slave Module IMDSM05 Digital I O Slave Module IMDSO01 IMDSO02 IMDSO03 and IMDSO04 Digital Slave Output Module IMFCS01 Frequency Counter...

Страница 4: ...inal D 1 through D 3 Original E 1 through E 2 Original F 1 through F 2 Original G 1 through G 2 Original H 1 through H 3 Original I 1 through I 2 Original Index 1 Original When an update is received i...

Страница 5: ...door of the cabinet containing these externally powered circuits must be marked with a warning stating that multiple power sources exist p 2 6 SPECIFIC CAUTIONS Remove modules slave master or terminat...

Страница 6: ...d entree l alimentation Le cas echeant un avertissement signalant la presence de sources d alimentation multiples doit entre appose sur la porte de l armoire p 2 6 ATTENTIONS D ORDRE SP CIFIQUE Retire...

Страница 7: ...nal Wiring 2 5 SECTION 3 MAINTENANCE 3 1 INTRODUCTION 3 1 MAINTENANCE SCHEDULE 3 1 SECTION 4 REPAIR REPLACEMENT PROCEDURES 4 1 INTRODUCTION 4 1 MODULE REPLACEMENT PROCEDURES 4 1 SECTION 5 SUPPORT SERV...

Страница 8: ...Module Application 1 2 2 1 NIDI01 Termination Module Layout 2 2 2 2 NIDI01 Cable Connections 2 3 2 3 NIDI01 Terminal Strip Assignments 2 7 2 4 Example System PoweredDigital Input Connections 2 8 2 5 E...

Страница 9: ...ault Output Values D 2 D 2 IMDSM05 Switch S2 Default Output Values D 2 D 3 IMDSM05 Switch S3 I O Configuration D 2 D 4 IMDSM05 Switch S4 Address Examples D 3 D 5 IMDSM05 Switch S5 Address Switch D 3 D...

Страница 10: ...mination module into operation Do not put the IDI termination module into opera tion until this instruction is read and understood INSTRUCTION CONTENT This manual contains five sections and nine appen...

Страница 11: ...tion after the mod ule is operating GLOSSARY OF TERMS AND ABBREVIATIONS Table 1 1 lists the definitions of terms and abbreviations used in this instruction Figure 1 1 Example NIDI01 Termination Module...

Страница 12: ...ties MMU Module mounting unit A card cage that provides electrical and communication support for INFI 90 Network 90 modules Termination Module TM Provides input output connection between plant equipme...

Страница 13: ...at least one round cable is connected to the termination mounting unit Table 1 4 Specifications Property Characteristic Value Power Requirements 24 VDC from 24 VDC bus bar of the termination mounting...

Страница 14: ...1 Do not use the NKTM01 cable when compliance with IEEE 472 1974 is necessary 2 Refer to the Hydraulic Servo Slave Module instruction manual for more details about input and output signal requirement...

Страница 15: ...equipment and static safe practices when working with modules 1 Use Static Shielding Bag Keep the modules in the static shielding bag until you are ready to install them in the system Save the packagi...

Страница 16: ...ATION This section explains how to configure and install the IDI ter mination module The required procedures are jumper configu ration installing the termination module itself cable connections and te...

Страница 17: ...Jumper J1 through J10 Settings Master Slave Module Type Jumper Position 1 2 3 4 5 6 7 8 9 10 IMASO01 1 0 1 0 1 0 1 0 1 0 IMDSI02 IMDSO04 1 0 1 0 1 0 1 0 1 0 IMDSM04 0 0 0 0 0 0 0 0 0 1 IMDSM05 0 1 0 1...

Страница 18: ...master or slave module 61 m 200 ft NKTU12 non PVC Termination Cable NKTM01 Ribbon Communication Cable Connects the IDI module to the master or slave module P1 of the IDI module to P3 of the master or...

Страница 19: ...s are installed in the termination mounting unit Installing the Termination Module The IDI termination module inserts into a standard INFI 90 ter mination mounting unit and occupies one slot To instal...

Страница 20: ...ing system power at the power entry panel then the door of the cabinet containing these externally powered circuits must be marked with a warning stating that multiple power sources exist AVERTISSEME...

Страница 21: ...NOT USED NOT USED SIM MODE NOT USED LVDT SEC 1 NOT USED NOT USED NOT USED NOT USED NOT USED INPUT NOT USED SERVO 2 NOT USED NOT USED NOT USED 8B 8B 8B 7B 7B 7B 1 2 1 2 7B 8B 7B 8B 7B 8B CH8 EMER MAN...

Страница 22: ...Example System Powered Digital Input Connections Figure 2 5 Example Field Powered Digital Input Connections SYSTEM POWER FUSE NIDI01 FIELD CONTACTS COMMON BUS BAR IN TERMINATION MOUNTING UNIT T00517A...

Страница 23: ...MAINTENANCE SCHEDULE Execute the tasks in Table 3 1 at the specified intervals Table 3 1 Maintenance Schedule Task Interval Clean and tighten all power and field wir ing connections Every 6 months or...

Страница 24: ...of the defective IDI module 6 Connect all wiring removed in Step 3 to the replacement IDI module 7 Verify proper wiring connections to the replacement IDI module 8 Insert the replacement IDI module un...

Страница 25: ...REPAIR REPLACEMENT PROCEDURES MODULE REPLACEMENT PROCEDURES 4 2 I E96 410A 10 Apply power to the cabinet containing the replacement IDI module...

Страница 26: ...and quantity 2 Model and serial numbers if applicable 3 Bailey Controls Company instruction manual number page number and reference figure that identifies the part Order parts without commercial desc...

Страница 27: ...onfigura tion consists of setting the slave module address dipswitch S1 and the analog output mode dipswitches S2 through S15 Refer to the IMASO01 Analog Slave Output Module instruc tion manual for de...

Страница 28: ...5 8 6 4 7 2 8 1 0 0 0 0 0 0 0 0 0 16 0 0 0 1 0 0 0 0 32 0 0 1 0 0 0 0 0 48 0 0 1 1 0 0 0 0 63 0 0 1 1 1 1 1 1 NOTES 0 CLOSED or ON 1 OPEN or OFF 1 Switch positions 1 and 2 must remain CLOSED Table A 2...

Страница 29: ...J32 Refer to the IMDSI02 Digital Slave Input Module instruction manual for detailed instructions Figure B 1 IMDSI02 Digital Slave Input Module GROUP A LEDs ADDRESS SWITCH DIGITAL INPUT TYPE JUMPER P1...

Страница 30: ...3 4 2 3 3 4 3 4 6 6 22 1 2 1 2 2 3 2 3 2 3 3 4 3 4 2 3 3 4 3 4 7 7 23 1 2 1 2 2 3 2 3 2 3 3 4 3 4 2 3 3 4 3 4 8 8 24 1 2 1 2 2 3 2 3 2 3 3 4 3 4 2 3 3 4 3 4 Group B 1 9 25 1 2 1 2 2 3 2 3 2 3 3 4 3 4...

Страница 31: ...iguration consists of setting the slave module address dipswitch S1 enabling disabling input preamplifiers slide switches S2 and S3 setting digital input voltage levels jump ers J1 through J8 and sett...

Страница 32: ...ust be selected when using a preamplifier Table C 3 IMDSM04 Jumpers J1 through J8 Digital Input Voltage Levels Jumper Number Jumper Setting Preamplifier Condition Current Range Voltage Range J1 A B B...

Страница 33: ...RATION INTRODUCTION I E96 410A C 3 Table C 4 IMDSM04 Jumpers J9 through J16 Voltage Response Times Jumper Position DC Voltage Response Time D 8 5 msecs debounce time slow response C No debounce time f...

Страница 34: ...h S3 slave module address dipswitch S4 enable disable address switch dipswitch S5 digital input type jumpers J1 through J16 and master module type jump ers J17 and J18 Refer to the IMDSM05 Digital I O...

Страница 35: ...er during default conditions 0 No output signal will be sent during default NOTE 0 CLOSED or ON 1 OPEN or OFF Table D 3 IMDSM05 Switch S3 I O Configuration Switch Position Function 1 2 3 4 1 Set Group...

Страница 36: ...ction 1 21 1 Enable contacts 1 4 of the address switch 0 Disable contacts 1 4 of the address switch 1 Enable contacts 5 8 of the address switch 0 Disable contacts 5 8 of the address switch NOTE 0 CLOS...

Страница 37: ...provided as a quick reference guide for person nel installing the NIDI01 termination module Configuration consists of setting the slave module address dipswitch S1 Refer to the IMDSO01 02 03 Digital...

Страница 38: ...Binary Value 11 128 21 64 3 32 4 16 5 8 6 4 7 2 8 1 0 0 0 0 0 0 0 0 0 16 0 0 0 1 0 0 0 0 32 0 0 1 0 0 0 0 0 48 0 0 1 1 0 0 0 0 63 0 0 1 1 1 1 1 1 NOTES 0 CLOSED or ON 1 OPEN or OFF 1 Switch positions...

Страница 39: ...rovided as a quick reference guide for person nel installing the NIDI01 termination module Configuration consists of setting the slave module address dipswitch S1 Refer to the IMDSO04 Digital Slave Ou...

Страница 40: ...DSO04 Switch S1 Address Examples Address Example Switch Position Binary Value 11 128 21 64 3 32 4 16 5 8 6 4 7 2 8 1 0 0 0 0 0 0 0 0 0 16 0 0 0 1 0 0 0 0 32 0 0 1 0 0 0 0 0 48 0 0 1 1 0 0 0 0 63 0 0 1...

Страница 41: ...the dipswitch settings to configure the module This information is provided as a quick reference guide for per sonnel installing the NIDI01 termination module Configura tion consists of setting the sl...

Страница 42: ...A Table G 1 IMFCS01 Switch S1 Address Examples Address Example Switch Position Binary Value 1 128 2 64 3 32 4 16 5 8 6 4 7 2 8 1 0 0 0 0 0 0 0 0 0 50 0 0 1 1 0 0 1 0 100 0 1 1 0 0 1 0 0 150 1 0 0 1 0...

Страница 43: ...er bus address dipswitch S1 controller gain dipswitch S2 oscillator fre quency dipswitch S3 oscillator amplitude dipswitch S4 LVDT excitation voltage dipswitch S5 and demodulator gain dipswitch S6 Ref...

Страница 44: ...tions Function 1 2 3 4 5 6 7 8 0 1 1 1 1 1 1 1 Amplifier gain of 20 50 1 0 1 1 1 1 1 1 Amplifier gain of 18 25 1 1 0 1 1 1 1 1 Amplifier gain of 15 05 1 1 1 0 1 1 1 1 Amplifier gain of 13 10 1 1 1 1 0...

Страница 45: ...0 CLOSED or ON 1 OPEN or OFF Do not leave both switches open Table H 6 IMHSS02 Switch S6 Demodulator Gain Switch Positions Function 1 2 3 4 5 6 7 8 0 1 1 1 1 1 1 1 Amplifier gain of 150 1 0 1 1 1 1 1...

Страница 46: ...rence guide for personnel installing the NIDI01 ter mination module Configuration consists of setting the module address dipswitch S2 and digital input type jumpers J1 through J8 Refer to the IMLMM02...

Страница 47: ...NOTE 0 CLOSED or ON 1 OPEN or OFF Table I 2 IMLMM02 Switch S2 Module Address Address Example Switch Position Binary Value 4 16 5 8 6 4 7 2 8 1 0 0 0 0 0 0 8 0 1 0 0 0 16 1 0 0 0 0 24 1 1 0 0 0 31 1 1...

Страница 48: ...nfiguration E 1 IMDSO04 configuration F 1 IMFCS01 configuration G 1 IMHSS02 configuration H 1 IMLMM02 configuration I 1 Installation 2 2 Instruction content 1 1 Intended user 1 1 J Jumpers 2 2 M Maint...

Страница 49: ...8756 ASIA PACIFIC 152 Beach Road Gateway East 20 04 Singapore 189721 Telephone 65 391 0800 Telefax 65 292 9011 EUROPE AFRICA MIDDLE EAST Via Puccini 2 16154 Genoa Italy Telephone 39 10 6582 943 Telefa...

Отзывы: