INTRODUCTION
NOMENCLATURE
1 - 4
I-E96-435A
®
NOMENCLATURE
contains the modules and equipment that can be
used with the NIAI03 module:
SPECIFICATIONS
Refer to Table
for the specifications of the NIAI03 termina-
tion module.
Table 1-3. Nomenclature
Nomenclature
Description
IMASM03
Analog Input Master Module
NKTM01
Cable, Termination Unit (Ribbon Cable)
NKTU02
Cable, Termination Unit (PVC)
NKTU12
Cable, Termination Unit (non-PVC)
258436A1
Cable retaining kit used when a round cable connects to
the TMU.
NTMU01
Termination Mounting Unit (Rear Mount)
NTMU02
Termination Mounting Unit (Front Mount)
Table 1-4. Specifications
Property
Characteristic/Value
Power Requirements
+24 VDC at 10 mA.
Mounting
Slides into a single slot in NTMU01/02.
Environmental:
Electromagnetic/Radio
Frequency Interference
Ambient Temperature
Relative Humidity
Atmospheric Pressure
Air Quality
No values available at this time. Keep cabinet doors closed. Do not use
communication equipment closer than 2 meters from the cabinet.
0
o
to 70
o
C (32
o
to 158
o
F).
5% to 90%
±
5% up to 55
o
C (131
o
F) (noncondensing).
5% to 40%
±
5% up to 70
o
C (158
o
F) (noncondensing).
Sea level to 3 km (1.86 mi).
Noncorrosive.
Cooling Requirements
No cooling is necessary when used in Bailey Controls cabinets and oper-
ated within stated limits.
Surge Protection
Meets IEEE-472-1974 Surge Withstand Capability Test
1
.
Certification
CSA certified for use as process control equipment in an ordinary (non-
hazardous) location.
NOTE: 1. Do not use the NKTM01 cable when compliance with IEEE-472-1974 is necessary.
Specifications are subject to change without notice.