INSTALLATION
SETUP/PHYSICAL INSTALLATION
I-E96-435A
2 - 3
To install the cable follow these steps.
1. If it has already been installed, pull the termination module
several inches from the MMU backplane.
2. If round type cables are already installed in the TMU,
remove the cable retaining bracket (Bailey part number
258436A1). Use NKTU02/12 or NKTM01 cables. Round cables
and ribbon cables can be mixed when installing multiple TMs.
3. Insert the J2 end of the termination module cable into the
MMU backplane slot assigned to the slave module. The cable
should latch securely in place. Card edge connector P3 of the
slave module connects to this end of the cable.
4. If NKTU02 or NKTU12 cables are used, connect the shield
wire extending from the J2 end of the cable to the shield bar.
5. Insert the J1 end of the cable into the TMU backplane slot
assigned to the NIAI03 module. The cable should latch
securely in place. Card edge connector P1 of the NIAI03 module
connects to this end of the cable.
6. Replace or add the cable retaining bracket if round type
cables (NKTU02/12) are installed in the TMU.
Termination Module Installation
The NIAI03 inserts into a standard INFI 90 termination mount-
ing unit (TMU) and occupies one slot. To install:
1. Verify slot assignment of the NIAI03 module.
2. Align the NIAI03 module with the guide rails in the TMU
and partially insert the module. Leave enough room to connect
terminal wiring and cables.
Completely seat the module after cabling and termination wir-
ing is attached.
CAUTION
Remove modules from their module mounting unit slots before
installing or removing a cable assigned to that slot. Failure to
do so could result in damage to the module.
ATTENTION
Retirer le module de son emplacement dans le chassis de
montage des modules avant d'installer ou de retirer un câble
assigne a cet emplacement. Un manquement à cette procédure
pourrait endommager le module.