INSTALLATION
SETUP/PHYSICAL INSTALLATION
2 - 4
I-E96-434A
®
To install the cable follow these steps:
1. Pull the termination module several inches from the TMU
backplane.
2. If round type cables are already installed in the TMU,
remove the cable retaining bracket (Bailey part number
258436A1). Use NKTU02/12 or NKTMU01 cables. Round
cables and ribbon cables can be mixed when installing multi-
ple TMs.
3. Insert the J2 end of the termination module cable into the
MMU backplane slot assigned to the slave module. The cable
should latch securely in place. Card edge connector P3 of the
slave module connects to this end of the cable.
4. If NKTU02 or NKTU12 cables are used, connect the shield
wire extending from the J2 end of the cable to the shield bar.
5. Insert the J1 end of the cable into the TMU backplane slot
assigned to the NIAI02 module. The cable should latch
securely in place. Card edge connector P1 of the NIAI02 module
connects to this end of the cable.
6. Up to four NIAI02 TMs (1-4) can be interconnected by con-
necting J2 on the first TM to J1 on the second TM with ribbon
cable part number 6634408A2. Install the 6634408A2 cable
for each NIAI02.
7. Connect J1 of the first NIAI02 in the interconnection with
TM-1 through TM-4 to J1 on the NIAM02.
8. Up to four additional NIAI02 TMs (5-8) can be intercon-
nected by connecting J2 on the first TM to J1 on the second TM
with ribbon cable part number 6634408A2. Install the
6634408A2 cable for each NIAI02.
9. Connect J1 of the first NIAI02 in the interconnection with
TM-5 through TM-8 to J2 on the NIAM02.
10. Replace or add the cable retaining bracket if round type
cables are installed in the TMU.
CAUTION
Remove modules from their assigned slots before installing a
cable to that slot. Failure to do so could result in damage to the
module or station.
ATTENTION
Retirer les modules de leur position assignée avant d'installer
un câble à cette position. Des dommages au module ou au
poste pourraient résulter d'un manquement à cette procédure.