INSTALLATION
SETUP/PHYSICAL INSTALLATION
2 - 6
I-E96-434A
®
Power Wiring
Connect field inputs with 14 to 22 gauge wire. To connect field
wiring follow these steps:
1. Remove the front cover.
2. Ensure the NIAI02 module is pulled out far enough to gain
access to the terminal strip.
3. Feed the field wiring into the terminal strip area and con-
nect them to the appropriate terminals.
4. Insert the module until it locks securely into place.
5. Replace the front cover to maintain thermal stability for the
local cold junction reference RTD.
The NIAI02 is ready for operation if:
1. The circuit board is mounted in the termination mounting
unit.
2. All required cables are connected to the termination mod-
ule.
3. All required field wires are connected to the termination
module.
CAUTION
If input or output circuits are a shock hazard after disconnect-
ing system power at the power entry panel, then the door of the
cabinet containing these externally powered circuits must be
marked with a warning stating that multiple power sources
exist.
ATTENTION
Si des circuits d'entree ou de sortie sont alimentes a partir de
sources externes, ils presentent un risque de choc electrique
meme lorsque l'alimentation du systeme est debranchee du
panneau d'entree l'alimentation. Le cas echeant, un avertisse-
ment signalant la presence de sources d'alimentation multiples
doit etre appose sur la porte de l'armoire.