OPERATING PROCEDURES
START-UP PROCEDURES
4 - 2
I-E96-316A
®
START-UP PROCEDURES
The Multi-Function Processor (MFP) controls the start-up of
the QRS module; it is fully automatic. Function Code (FC) 79 in
the MFP configuration enables the QRS. Specification 1 (FC 79)
is the slave module address. It must be the same as the
address set on the address dipswitch (S1). The front panel LED
(solid green) verifies that the module is enabled and communi-
cating.