background image

DESCRIPTION AND OPERATION

LOGIC POWER

2 - 4

  

WBPEEUI240754A0

®

Status Data

Status data consists of three separate 8-bit bytes read by the
control module. The first byte contains readback data that
reflects the state of the relays. The second byte is not significant,
it exists to have compatibility with the other DSO modules.

The third byte is the module identification and module status.
I/O module identification is in the four most significant bits
(MSB). It identifies the I/O module to the control module. It also
verifies the I/O expander bus communication integrity and the
control module configuration. I/O module status is the least
significant bit (LSB). During initialization, the control module
writes data to the output register and default register, and
forces this bit to a logic 1. A reset or 

time-out

 (bus fault error)

resets it to a logic 0. Default data is normally written only dur-
ing control module start-up. The control module reads the mod-
ule status bit to test for a change in the state of the module. It
uses this bit as a signal to rewrite data to the module to ensure
that proper default values are in the default register.

Output Data

Output data is one 8-bit byte sent to the output register. Each
bit of data represents one output. The bit value reflects the state
of the output. Logic 1 turns a field device ON; logic 0 turns it
OFF.

Default Data

Default data is one 8-bit byte sent to the default register. It is
set by the control module configuration (FC 128). The function
of this data is the same as the output data but is used only
when a 

time-out

 occurs.

LOGIC POWER

Logic power (+5 VDC) drives the DSO circuits. It connects
through the top 12-pin card edge connector (P1) shown in
Figure

2-1

.

RELAY POWER

Relay power (+24 VDC) drives the on-board relays. It connects
through the 30 pin card edge connector (P3) shown in Figure
2-1. The power line is protected against polarity inversion due
to a cabling error on the termination unit (TU) or termination
module (TM).

NOTE:  Logic power ground and relay power ground are tied
together inside the module. 

Содержание Infi 90 IMDSO15

Страница 1: ...Process Control and Automation Solutions from Elsag Bailey Group IMDSO15 Digital Output Module...

Страница 2: ...NIQUES SONT SENSIBLES AUX PERTURBATIONS PAR FR QUENCE RADIO DES PR CAUTIONS DEVRONT TRE PRISES LORS DE L UTILISATION DU MAT RIEL DE COMMUNICATION PORTATIF LA PRUDENCE EXIGE QUE LES PR CAUTIONS PRENDRE...

Страница 3: ...module The IMDSO15 mod ule provides electromechanical relay changeover contacts for field devices Refer to product instruction I E96 310 for information on the IMDSO01 02 03 Refer to product instruct...

Страница 4: ...6 4 Original 7 1 Original 8 1 Original A 1 through A 2 Original B 1 through B 2 Original C 1 through C 2 Original Index 1 through Index 2 Original When an update is received insert the latest changed...

Страница 5: ...NNECTIONS 2 3 I O EXPANDER BUS 2 3 UNIVERSAL I O EXPANDER BUS INTERFACE 2 3 MODULE DATA 2 3 Status Data 2 4 Output Data 2 4 Default Data 2 4 LOGIC POWER 2 4 RELAY POWER 2 4 BUS FAULT TIMER 2 5 STATUS...

Страница 6: ...DURES 6 2 Printed Circuit Board Cleaning 6 2 General Cleaning and Washing 6 3 Edge Connector Cleaning 6 3 Checking Connections 6 3 SECTION 7 REPAIR REPLACEMENT PROCEDURES 7 1 INTRODUCTION 7 1 MODULE R...

Страница 7: ...le Page 1 1 Glossary of Terms and Abbreviations 1 4 1 2 Reference Documents 1 4 1 3 Nomenclature 1 5 1 4 Related Hardware 1 5 1 5 Module Specifications 1 5 1 6 Relay Specifications 1 7 3 1 S1 Address...

Страница 8: ...connector pins p 5 2 Never clean electrical parts or components with live power present Doing so exposes you to an electrical shock hazard p 6 2 Wear eye protection whenever working with cleaning solv...

Страница 9: ...i Trademarks and Registrations Registrations and trademarks used in this document include INFI 90 Registered trademark of Elsag Bailey Process Automation INFI NET Registered trademark of Elsag Bailey...

Страница 10: ...l relays provide changeover contacts for field devices Con trol modules perform the control functions I O modules provide the input output functions Figure 1 1 illustrates the INFI 90 OPEN communicati...

Страница 11: ...t red LEDs display the module relay states active non active The DSO module has three card edge connectors for external signals and power P1 P2 and P3 P1 connects to logic power 5 VDC that drives the...

Страница 12: ...C provides a quick reference for switch location and settings HOW TO USE THIS MANUAL Read this instruction before handling the IMDSO15 digital out put module Refer to a specific section for informati...

Страница 13: ...ator con sole with data acquisition and reporting capabilities It provides a digital access into the process for flexi ble control and monitoring TM Termination module Provides input output direct con...

Страница 14: ...e Description IMMFP01 02 03 03B Multi function processor module IMLMM02 Logic master module NIDI01 Termination module digital inputs NTDI01 Termination unit digital inputs NKTM01 Cable termination mod...

Страница 15: ...dio frequency field 900 5 MHz ENV 50204 Unmodulated rms 10 V m Pulse modulated Duty cycle 50 Rep cycle 200 Hz Radio frequency common mode amplitude modulated 0 15 MHz to 80 MHz ENV 50141 Unmodulated r...

Страница 16: ...ironment EN50082 2 Generic Immunity Standard Part 2 Industrial Environment EN 61010 Safety Requirements for Electrical Equipment for Measurement Control and Laboratory Use Part 1 General Requirements...

Страница 17: ...module operating status back to a control module Electromechanical relays provide the switching functions Figure 2 1 is a block diagram of the DSO module It illustrates signal flow through the module...

Страница 18: ...ion FC 83 specifi cation S2 The bus fault detector in the I O expander bus interface checks for a time out condition During a time out the data selector block normally selects the default register dat...

Страница 19: ...us between the control and I O modules Cable assemblies can extend the bus to six MMUs A control module and its I O modules form an individual sub system within a process control unit PCU The I O expa...

Страница 20: ...module reads the mod ule status bit to test for a change in the state of the module It uses this bit as a signal to rewrite data to the module to ensure that proper default values are in the default...

Страница 21: ...ult timer times out in 10 milliseconds This causes the digital outputs to change to their default values A red front panel status LED indicates a bus fault time out STATUS LED INDICATOR Two front pane...

Страница 22: ...devices by electro static discharge Use the static grounding wrist strap when installing and removing modules Static discharge may damage static sensi tive devices on modules in a cabinet Use grounde...

Страница 23: ...TUP PHYSICAL INSTALLATION Prior to installation set the S1 address switch Configure the termination unit TU or termination module TM to output the digital signals from the DSO to the field devices Ref...

Страница 24: ...TP65205B NOTE OPEN POSITION LOGIC 1 Table 3 1 S1 Address Switch Settings ADDR MSB LSB ADDR MSB LSB 3 4 5 6 7 8 3 4 5 6 7 8 0 0 0 0 0 0 0 14 0 0 1 1 1 0 1 0 0 0 0 0 1 15 0 0 1 1 1 1 2 0 0 0 0 1 0 16 0...

Страница 25: ...90 OPEN module mounting unit MMU and occupies one slot To install 1 Verify the slot assignment of the module 2 Verify that a dipshunt is in the I O expander bus socket on the MMU backplane between th...

Страница 26: ...ic power establish I O expander bus communication and provide digital outputs P1 P2 P3 respectively Wiring Installing the module in the MMU connects the digital output module to the logic power 5 VDC...

Страница 27: ...board fusing requirements PREOPERATING ADJUSTMENTS The IMDSO15 digital output module does not require any adjustments prior to operation Figure 3 3 Cable Connections and Terminations T00276A P1 P1 P3...

Страница 28: ...ED indi cators to aid in system test and diagnosis Eight front panel indicators display the relay states active or non active The location of the indicators is shown in Figure 4 1 Module Status Indica...

Страница 29: ...SO module it is fully automatic Function Code FC 83 in the control mod ule configuration enables the DSO Specification 1 of FC 83 is the module address It must be the same as the address set on the S1...

Страница 30: ...ndicate normal operation and error conditions Table 5 1 lists DSO status LED states error indications probable causes and cor rective actions NOTE If the corrective actions in Table 5 1 do not correct...

Страница 31: ...t on switch S1 is the same as the address in FC 83 specification S1 If not 1 Drive the module s relays to a non active status 2 Disconnect the relay power supply 24 VDC 3 Remove the module and change...

Страница 32: ...it and the digital output module Verify the bus connection on the MMU backplane If the I O module is faulty replace it with a new one Refer to the REPAIR REPLACEMENT PROCEDURES in Section 7 for proce...

Страница 33: ...Data 6 9 Clock 10 Sync 11 NC 12 NC NC Not connected Table 5 4 P3 Signal Pin Connections Output Channel Pin COM 1 Pin NO 1 PIN NC 1 1 A 1 B 2 2 C 3 3 D 4 E 4 5 F 6 5 K 9 L 6 10 M 11 7 N 12 P 8 13 R 14...

Страница 34: ...uipment Maintenance personnel should be familiar with the module mounting unit have experience working with process con trol systems and know what precautions to take when working on live AC and or DC...

Страница 35: ...rk stations Always observe the steps under SPECIAL HANDLING in Section 3 when handling printed cir cuit boards Table 6 1 Preventive Maintenance Schedule Task Frequency Check cabinet module mounting un...

Страница 36: ...99 5 electronic grade and 20 distilled water 2 Soak a lint free cloth with the solvent mixture 3 Work the cloth back and forth parallel to the edge connector contacts 4 Repeat with a clean cloth that...

Страница 37: ...ning action will verify that it is secure There must not be any motion done to loosen the connection 1 Verify that all power connections within the cabinet are secure 2 Verify that all wiring connecti...

Страница 38: ...urn to unlatch the module It is unlatched when the slots on the screws are vertical and the open end of the slots face away from the module 4 Gently slide the module out of the MMU 5 Configure the rep...

Страница 39: ...utomation sales office Provide the following information 1 Part description part number and quantity 2 Model and serial number if applicable 3 Elsag Bailey instruction number and page number of part r...

Страница 40: ...pplication Table A 2 provides the relay contact assignments and Figure A 1 shows the location of those relay contacts Refer to this figure when connecting field wiring to the NTDI01 Table A 1 NTDI01 D...

Страница 41: ...ble A 2 Relay Contact Assignment continued Signal NTDI01 Terminal No Figure A 1 Relay Contact Terminal Block Assignment TERMINAL NUMBER TB4 TB2 TB1 TB3 DIPSHUNT USED XU13 XU14 XU15 XU16 TP80663A 1 2 3...

Страница 42: ...the relationship between the DSO module signals and the NIDI01 terminal numbers Figure B 1 shows the terminal assignment location for the digital out put signals Disregard the markings on the terminal...

Страница 43: ...Terminal Assignments T00275A 32 1 3 5 6 7 8 9 10 11 12 13 14 15 16 17 4 19 20 21 22 23 24 18 25 26 27 28 29 30 31 2 CH 8 CH 7 CH 6 CH 5 CH 4 CH 3 CH 2 CH 1 C O M 1 2 4 V C O M M O N N O T U S E D N C...

Страница 44: ...ut module Refer to SETUP PHYSICAL INSTALLATION in Section 3 for a complete description of switch settings Figure C 1 S1 Address Switch Location MODULE STATUS LEDs ADDRESS SWITCH OUTPUT STATUS LEDs EDG...

Страница 45: ...0 1 0 1 0 11 0 0 1 0 1 1 43 1 0 1 0 1 1 12 0 0 1 1 0 0 44 1 0 1 1 0 0 13 0 0 1 1 0 1 45 1 0 1 1 0 1 14 0 0 1 1 1 0 46 1 0 1 1 1 0 15 0 0 1 1 1 1 47 1 0 1 1 1 1 16 0 1 0 0 0 0 48 1 1 0 0 0 0 17 0 1 0...

Страница 46: ...y 1 4 I I O expander bus 1 4 Installation 3 2 3 4 Module 3 4 Termination devices 3 5 Instruction content 1 2 Intended user 1 2 Isolation specifications 1 6 L Logic master module 1 4 M Maintenance 6 1...

Страница 47: ...S1 switch 3 2 Special handling 3 1 Start up procedures 4 2 Status LED indicators 4 1 5 1 T Technical documentation 8 1 Termination configuration Termination module TM 3 4 Termination unit TU 3 4 Termi...

Страница 48: ...6 ASIA PACIFIC 152 Beach Road Gateway East 20 04 Singapore 189721 Telephone 65 391 0800 Telefax 65 292 9011 EUROPE AFRICA MIDDLE EAST Via Puccini 2 16154 Genoa Italy Telephone 39 10 6582 943 Telefax 3...

Отзывы: