24V motor control device for flush box mounting - Version 1.1
Instruction manual
13/22
6
Initial operation
w w w .b ai e r- g mb h .d e
6.1
Configuration
N O T I C E
Overtightened potentiometer
Damage of control device may result in malfunction.
Potentiometers have a right and a left stop, which must not
be overtightened.
Adjust potentiometer only with low force and with an
appropriate screw driver.
Hint
Changes in configuration when the initial operation is done, will force
the control device to perform a new initial operation.
Perform initial operation, refer to chapter 6.2
6.1.1
Tolerance of power operated shutdown
In some cases the drive will not shut down correctly during or after initial operation.
Or the drive stops, before it has reached the end position. This particularly happens,
when a very heavy or a very lightweight wing is used.
N O T I C E
Motor overload
Damage of components by motor overload.
Check after any change of configuration, if the control
device shuts down correctly.
Do not set tolerance too high.
When the drive stops early
Turn potentiometer 1 clockwise
Drive switches off later
When the drive does not stop
Turn potentiometer 1 counterclockwise
Drive switches off sooner
Hint
After a maximum time of 5 minutes, the drive switches off in each case.
Increase tolerance
Decrease tolerance