79
8.3
Data interface Com1 and Com2
The optional data interface can be used for data retrieval on site with data
retrieval software (e.g. SIGLON) or to connect to an external modem. The
baud rate can be set with DLXPARA to a value between 300 and 9600
baud. It is implemented as a 25 pin SUB-D connector (female) according to
ISO2110, the pin allocation is according to V.24/RS232C/DIN 66020.
Alternatively a 25 pin SUB-D male connector, a bus interface (20mA/CS,
M-Bus or RS485) or a FO connector (fiber-optic transmission connection)
can be used.
8.3.1
Pin allocation RS232 SUB-D (female)
The standard pin allocation of the data interface is identical with the service
interface (see page 78). For the connection between the DLX and a PC, a
modem cable is required. For the connection between a DLX and an exter-
nal modem a so-called null modem cable (crossed wires) is required.
8.3.2
Pin allocation RS232 SUB-D (male)
For the connection between the DLX and a PC, a null modem cable
(crossed wires) is required. For the connection between a DLX and an ex-
ternal modem a modem cable is required (1 to 1).
DLX (25 pins, male)
cable
PC (25 pins, male)
Input/Output
Pin No.
Pin No. Input/Output Standard usage
Output
2
2
Output
TxD (transmit data)
Input
3
3
Input
RxD (receive data)
Output
4
4
Output
RTS (request to send)
Input
5
5
Input
CTS (clear to send)
7
7
GND (protective earth)
Input
6
6
Input
DSR (data set ready)
Output
20
20
Output
DTR (data terminal ready)
8.3.3
Pin allocation RS232 (Com1/X6 at 19”-rack only)
For the connection between the DLX and a PC, a special cable (5 wires) is
required.
Identification: Phoenix 5 pins PSC 1,5/5-M.
DLX (5 pins, male)
cable
PC (25 pins, male)
Input/Output Pin No.
Pin No. Input/Output Standard usage
Input
1
4
Output
RTS
Input
2
2
Output
TxD
Output
3
3
Input
RxD
Output
4
5
Input
CTS
5
7
GND
Baud rate: 300 to 9600 Baud
Содержание DLX
Страница 9: ...9 1 Scope of Application 1 1 Application environment Figure 1 Application environment...
Страница 42: ...42 4 2 Installation diagram Figure 13 Dimensions of mounting points...
Страница 54: ...54 7 Menus 7 1 Flow diagram Figure 24 Flow diagram of menus...
Страница 110: ...Subject to change without notice...
Страница 111: ...E116012215052 Appendix A Data Retrieval Protocols...
Страница 112: ...A 2...
Страница 156: ...Subject to change without notice...
Страница 157: ...E116012215052 Appendix B Table Addresses...
Страница 158: ...B 2...
Страница 170: ...Subject to change without notice...
Страница 171: ...E116012215052 Appendix C List of Parameters and Constants...
Страница 172: ...C 2...
Страница 178: ...Subject to change without notice...