A 7
1.2
Register status in the registration period data block
In each registration period the DLX stores a register status of 1 byte (2
characters) for each entry in the periodic buffer. This status is stored in the
same format as the device status (hexadecimal notation):
Byte 1
Character 1
Character 2
Bit 7
Bit 6
0
Bit 4
0
0
0
0
Meaning of individual bits:
Byte-No.
Bit-No.
Description
Byte 1
Bit 7
Parameter change for this register by the user
Bit 6
Power failure, no data telegrams or errors from
analogue input for at least 60 seconds
Bit 4
Overflow of this register
1.3
Retrieval of events (spontaneous event buffer : 051-xx)
The messages have the following format:
PL
ETYPE
ETIME
EADR
OSTATE
NSTATE
PL:
Packet length (24 or 43 bytes)
ETYPE: Type of event. The following event types are possible:
A1 – Alarm has occurred
A3 – Power outage
C1 – Parameter or value changed on site
C2 – Parameter or value changed via remote connection
D1 – Time was set on site
D2 – Time was set via remote connection
D3 – Change from wintertime to summertime
D4 – Change from summertime to wintertime
ETIME: Timestamp of the event: YY MM DD hh mm (Year Month Day Hour Minute)
EADR:
Address of the information affected by the event (not applicable for mes-
sages such as “Time was set” or “Power failure”): 051xx, xx: number of the
entry in the spontaneous event buffer modulo 100.
OSTATE: Old state of the information affected by the event (not applicable for mes-
sages such as “Time was set” or “Power failure”), see the table in section
13 „Fault displays“.
NSTATE: New state of the information affected by the event, see the table in section
13 “Fault displays“.
Содержание DLX
Страница 9: ...9 1 Scope of Application 1 1 Application environment Figure 1 Application environment...
Страница 42: ...42 4 2 Installation diagram Figure 13 Dimensions of mounting points...
Страница 54: ...54 7 Menus 7 1 Flow diagram Figure 24 Flow diagram of menus...
Страница 110: ...Subject to change without notice...
Страница 111: ...E116012215052 Appendix A Data Retrieval Protocols...
Страница 112: ...A 2...
Страница 156: ...Subject to change without notice...
Страница 157: ...E116012215052 Appendix B Table Addresses...
Страница 158: ...B 2...
Страница 170: ...Subject to change without notice...
Страница 171: ...E116012215052 Appendix C List of Parameters and Constants...
Страница 172: ...C 2...
Страница 178: ...Subject to change without notice...