A 5
1
SCTM Protocol
The following sections describe the data format of telegrams during com-
munication using the SCTM protocol (Serial Coded Telemetering). The fol-
lowing conditions have to be observed:
•
transmission settings: 7 (bits), e (even parity), 1 (stop bit)
•
the substation address (US-Number) has 5 digits (can be programmed us-
ing DLXPARA) or 8 digits (from version 1.04.01 and up)
•
no point-to-point connection is possible without substation address
•
the length of the header is constant: 14 (or 17) bytes
•
broadcast commands and priority telegrams are not supported
•
a maximum of two registration periods (MP1/Tm1 and MP2/Tm2) is sup-
ported
The following data can be retrieved:
•
load profile data from registration period buffers (PP-01 for MP1 and PP-02
for MP2) with a maximum of 16 channels (demand, energy values or in-
crements/energy feed) per buffer and registration period
•
spontaneous event data, including alarm messages, status messages and
parameter changes
•
table data (addresses between 000-00 and 999-99)
1.1
Device status in the registration period data block
The DLX stores the device status for each completed registration period;
this data contains general information about the unit for that period. It con-
sists of 4 ASCII characters, representing 2 bytes (2 characters per byte).
Each character is coded in the hexadecimal system and contains 4 bits.
The following table describes the relations between the hexadecimal nota-
tion and the binary notation:
Hex
Binary
Hex
Binary
Hex
Binary
Hex
Binary
0
0000
4
0100
8
1000
C
1100
1
0001
5
0101
9
1001
D
1101
2
0010
6
0110
A
1010
E
1110
3
0011
7
0111
B
1011
F
1111
In the DLX unit the device status is contained in 2 bytes:
Byte 1
Byte 2
Character 1
Character 2
Character 3
Character 4
T-Bit U-Bit M-Bit A-Bit S-Bit
0
NP-Bit
L-Bit
0
1
0
0
0
0
0
0
Содержание DLX
Страница 9: ...9 1 Scope of Application 1 1 Application environment Figure 1 Application environment...
Страница 42: ...42 4 2 Installation diagram Figure 13 Dimensions of mounting points...
Страница 54: ...54 7 Menus 7 1 Flow diagram Figure 24 Flow diagram of menus...
Страница 110: ...Subject to change without notice...
Страница 111: ...E116012215052 Appendix A Data Retrieval Protocols...
Страница 112: ...A 2...
Страница 156: ...Subject to change without notice...
Страница 157: ...E116012215052 Appendix B Table Addresses...
Страница 158: ...B 2...
Страница 170: ...Subject to change without notice...
Страница 171: ...E116012215052 Appendix C List of Parameters and Constants...
Страница 172: ...C 2...
Страница 178: ...Subject to change without notice...