Motorized Linear Actuator
baelz 373-E07
7.6 Errors
7.6.1 Errors after an initialization run
Following a successful initialization run, only the green LED is lit.
If the red LED is flashing, this indicates an error following an unsuccessful initialization run.
The first error to occur during initialization is shown. If the green LED is lit, the unit had already
been initialized before the current initialization run. If the green LED is flashing, the unit had not
been successfully initialized previously.
The red LED shows errors occuring during initialization as follows:
Error code 1: interval interval etc.
Error code 2: interval interval etc.
etc. up to ...
Error code 8: interval interval
etc..
Following an initialization run, the red LED shows only initialization errors as long as DIP switch
12 is set to 1. This enables a clear differentiation between errors occuring during initialization
and those occuring during normal positioner operation. Setting DIP switch 12 from 1 back to 0
permits the red LED to show any normal operational errors instead of initialization errors which
may have occured.
Error code
Error
Corrective action
1 →
1 x
Invalid status of initialization run. Possible
cause: EMI (electromagnetic interference).
Remove source of interference.
2 →
2 x
Sensor malfunction at analogue input AI1:
No signal from potentiometer.
Check connection terminals 91, 92, 93
(see wiring diagram, Fig. 24, page 22).
Replace potentiometer if necessary.
3 →
3 x
Potentiometer value at AI1 too small.
Possible cause: EMI.
Remove source of interference.
Replace potentiometer if necessary.
4 →
4 x
Potentiometer value at AI1 too large.
Possible cause: EMI.
Remove source of interference.
Replace potentiometer if necessary.
5 →
5 x
Wrong direction of travel
Check motor (97, 98, 99) and potentiometer
(91, 92, 93) connections (see wiring diagram,
Remove source of interference.
6 →
6 x
Obstruction: potentiometer or motor not moving.
Check connections, set N↔S switch to "N",
remove any obstructions.
7 →
7 x
Stroke too long.
Fit actuator to a valve with nominal stroke
length < 22 mm.
8 →
8 x
Stroke too short.
Fit actuator to a valve with nominal stroke
length > 8,7 mm, remove any obstructions.