Programmer Parameters
4-20 mA Parameters
OTEE:
N
These parameters apply to the HR-E LCD 4-20 encoder .
The
4-20 mA Parameters
field
(
)
displays the parameters of the encoder analog control signal . The 4-20 mA output
signal is directly proportional to the meter rate of flow . For default measurement resolution values, see the Measurement
Resolution charts in the
High Resolution LCD Encoder User Manual
, available at
Figure 29: 4-20 mA Parameters
•
The
4 mA
field is always set to zero (0) . The register produces a 4 mA signal at zero flow .
•
The
20 mA Setting
field displays the flow rate setting . Set this parameter to the flow rate at which the output should
generate to maximum signal . In most cases, this is the maximum flow rate of the meter .
•
The
Damping Factor
is the value used to stabilize the analog output signal .
Page 17
May 2018
ENC-PM-02040-EN-03