Programmer Parameters

4-20 mA Parameters

OTEE:

N

These parameters apply to the HR-E LCD 4-20 encoder .

The 

4-20 mA Parameters

 field 

(

Figure 29

displays the parameters of the encoder analog control signal . The 4-20 mA output 

signal is directly proportional to the meter rate of flow . For default measurement resolution values, see the Measurement 

Resolution charts in the 

High Resolution LCD Encoder User Manual

, available a

www.badgermeter.com

 .

Figure 29:  4-20 mA Parameters

• 

The 

4 mA 

field is always set to zero (0) . The register produces a 4 mA signal at zero flow .

• 

The 

20 mA Setting 

field displays the flow rate setting . Set this parameter to the flow rate at which the output should 

generate to maximum signal . In most cases, this is the maximum flow rate of the meter .

• 

The 

Damping Factor

 is the value used to stabilize the analog output signal . 

Page 17 

May 2018

ENC-PM-02040-EN-03

Содержание HR-E LCD 4-20

Страница 1: ...High Resolution LCD Encoder Programmer HR E LCD HR E LCD 4 20 ENC PM 02040 EN 03 May 2018 Programmer Manual...

Страница 2: ...High Resolution LCD Encoder Programmer Page ii May 2018 ENC PM 02040 EN 03...

Страница 3: ...tiple Encoders 10 Programmer Parameters 11 Serial Field 11 Version Field 11 Meter Type Field 11 Meter Model Size Field 12 Unit of Measure Field 12 Billing Units Field 13 Digits from Encoder Field 13 V...

Страница 4: ...High Resolution LCD Encoder Programmer Page iv May 2018 ENC PM 02040 EN 03...

Страница 5: ...encoders 67660 001 Programming kit CD Kit includes IR head bracket and programmer software CD 68468 001 Programming kit USB Kit includes IR head bracket programmer software USB and programming cable U...

Страница 6: ...ugh bracket opening as shown in Figure 2 Figure 1 Slide bracket onto encoder Figure 2 Bracket attached to encoder top view 3 Place the optical head of the IR cable in the bracket with the nubs on the...

Страница 7: ...e click the LCD Programmer shortcut to start the software application The License Agreement displays the first time you access the software Figure 4 Software shortcut 3 Read the License Agreement and...

Страница 8: ...is received the software determines the encoder type and populates the Programmer screen data fields as shown in Figure 8 For more information see Encoder Types on page 9 If the encoder is programmed...

Страница 9: ...the top of the screen Software parameters that display on the screen vary depending on the device type Examples of completed Programmer screens for all three device types are displayed here Figure 11...

Страница 10: ...rent Settings If you make a change on the Programmer screen you must apply the change to the encoder With the IR head aligned click Apply Current Settings to program the new values to the encoder The...

Страница 11: ...nnot change this number Version Field The Version field Figure 15 is a read only field that displays the encoder version You cannot change the value in this field Figure 15 Serial and Version number M...

Страница 12: ...f the table Disc inches Model CSM inches Model TSM inches Model 5 8 5 8 x 3 4 LP 2 High Side 1 1 2 T160 5 8 5 8 x 3 4 M25 2 Low Side 2 T200 3 4 M35 3 High Side 3 T450 1 M40 3 Low Side 4 T1000 1 M55 4...

Страница 13: ...nits Digits from Encoder Field The Digits from Encoder field Figure 20 displays the number of digits the encoder is programmed to send to the endpoint These options include 4 5 6 7 8 and 9 digits Read...

Страница 14: ...both fields For TSM Turbo 12 20 inch meters the value shown in the Visual Reading field and Encoder Output field may not display correctly The programming value however is calculated correctly and wil...

Страница 15: ...Flow Time Deactivate 6 Digit Display The Deactivate 6 digit display field can be used to remove the 6 digit consumption display from the encoder automatic display See the High Resolution LCD Encoders...

Страница 16: ...Indicators pop up window displays Figure 26 2 To clear the indicators click Clear Indicators in the pop up window NOTE N The Clear Indicators button does NOT clear the Programmed indicator 3 Click Clo...

Страница 17: ...ement Resolution charts in the High Resolution LCD Encoder User Manual available at www badgermeter com Figure 29 4 20 mA Parameters The 4 mA field is always set to zero 0 The register produces a 4 mA...

Страница 18: ...EXITING THE SOFTWARE APPLICATION To exit and close the software application click the X in the top right corner of the software screen as shown in Figure 30 Figure 30 Click the X to exit software Pag...

Страница 19: ...Appendix APPENDIX Page 19 May 2018 ENC PM 02040 EN 03...

Страница 20: ...nstallation The Welcome screen displays Figure 31 Software Installer Wizard Welcome screen 2 Click Next The Select Installation Folder screen displays Figure 32 Software files location 3 Click Next to...

Страница 21: ...isplays briefly Then the Installation Complete screen displays Figure 34 Progress bar shows installation in progress 5 At the Installation Complete screen click Close to exit the installer The Program...

Страница 22: ...IR cable The example Figure 36 shows COM 7 for the IR cable connected with a USB to serial adapter Prolific USB to Serial Comm Port 2 Write down the COM port number for use with the Programmer softwa...

Страница 23: ...Programmer Manual INTENTIONAL BLANK PAGE Page 23 May 2018 ENC PM 02040 EN 03...

Страница 24: ...sq Angelina N 24 Colonia Guadalupe Inn CP 01050 M xico DF M xico 52 55 5662 0882 Europe Eastern Europe Branch Office for Poland Latvia Lithuania Estonia Ukraine Belarus Badger Meter Europe ul Korfante...

Отзывы: