Programming
100 Point Linearization
The FC-5000 flow monitor can be set up to linearize the output from an eligible
flow meter� The calibration data for a particular flow meter and the curve fitted
K-FACTOR and FREQ/VISC points are included when the meter, calibration and
FC-5000 unit are ordered from the factory�
To manipulate or enter the linearization parameters:
1� See
to select
Sine UVC Fixed v
or
Pulse UVC Fixed
v
as the sensor input type�
2� Navigate to
SYSTEM SETUP > ADVANCED SETUP > SENSOR INPUT >
FLOW SENSOR 1 CAL
�
3� Highlight
MULTI-POINT TABLE
and press
ENTEO
�
4� For each calibration point, press
F2
(f/v) to enter or edit the
f/v
or
F3
(kFct) to
enter or edit the
K-factor
value�
5� On the numeric entry screens, enter the value and press
ENTEO
to save the
value, then return to the previous screen�
OTEE:
N
Each entry, 1…100, represents each calibration data point� Any number
of points can be entered, up to 100� Leave the fields at 0�000 if no data
exists�
Flow Sensor Properties
1� Navigate to
SYSTEM SETUP > ADVANCED SETUP > SENSOR INPUT
�
2� Highlight
FLOW SENSOO 1 POOP
and press
ENTEO
�
3� Select and edit each option, as necessary�
The flow sensor properties are:
Option
Description
Ch 1 Bore Dia
Bore diameter of connected flow meter�
Ch 1 Dia� Unit
Unit of measure (in� or mm) associated with bore diameter�
Ch 1 Material
Construction material of the connected flow meter�
Ch 1 Smoothing
Smoothing coefficient� As the number increases, averaging
becomes greater� As the number decreases, it approaches the
raw reading�