D-BA-0000308.6.4
Operating instructions
Technical data and dimensional drawings
V05 / September 07, 2010
OI-39
7 Technical data and dimensional drawings
7.1 Interference resistance, UL approval
7.1.1 CE compliance
Electromagnetic compatibility EMC
The devices are intended as components for installation in machines and systems.
Adherence to the installation instructions warrants compliance with the
corresponding requirements for CE compliance of the entire machine/system
equipped with such components based on the EMC Directive 2004/108/EC.
Generic standards:
Immunity to interference
industrial environments
According to EN61000-6-2
Interference resistance
against discharge of static
electricity
Tested according to EN61000-4-2 Level 1-3
No malfunction or permanent impairment on the housing and
all interfaces
Tested according to
EN61000-4-3
HF field, AM modulated: 80 MHz to 1 GHz,
10 V/m
Interference resistance
against high-frequency
electromagnetic fields
EN61000-4-6
HF asymmetrical, AM modulated:
150 kHz to 80 MHz, 10 V/m
Interference resistance to
rapid transient electric
disturbances (burst)
Supply tested according to EN61000-4-4 Level 3
Interfaces tested according to EN61000-4-4 Level 4
Interference resistance to
surge voltages
Supply tested according to EN61000-4-5 Level 1
Interfaces tested according to EN61000-4-5 Level 2
Generic standards:
Interference emission
industrial environments
According to EN61000-6-4
Interference emission,
Radio interference
Tested according to EN55011 Class A
Resistance to supply
voltage failure (+24 VDC)
Tested according to IEC 1131-2
≤
10 ms/s without malfunction
Tab. 14: Electromagnetic compatibility (EMC)