MGS-350 Manual
40
6509-9000 Rev 1
Section 5. Troubleshooting
Symptom
Possible Cause(s)
Green LED off after
power up
•
Check power supply. Check wiring.
•
Check for proper voltage at CON1.
•
MGS-350 was possibly damaged. Check
by installing another MGS-350 to confirm
the fault.
Red light on, green led
off (indicates a fault)
•
Sensor may be disconnected from
printed circuit board. Check to see
sensor is properly inserted into board.
•
The sensor has been damaged or has
reached the end of life and needs to be
exchanged. Contact Bacharach for
instructions and support.
Alarms in the absence
of a leak; False alarms
•
Try setting an alarm delay.
•
Perform a bump test to ensure proper
operation.
•
Increase the response time delay to help
eliminate false alarms.
•
Try adjusting the zero setting.