15
15
Table 1.
Internal Volume and Minimum Recommended Flow and Heat Loss
Model
Total Internal
hCore
®
Heat
Transfer Technol-
ogy Volume (gal)
Minimum Flow
(GPM)
Equipment Heat
Loss (BTU/hour)
Equipment Heat
Loss with Op-
tional PCDs (BTU/
hour)
NXF-0403N-CS2TS-H1
27
24
52,706
24,402
NXF-0403N-CS2TS-H2
53
48
104,413
47,961
NXF-0403N-CS2TS-H3
79
72
155,120
70,693
NXF-0403N-CS2TS-H4
105
96
204,828
92,614
NXF-0403N-CS2TS-H5
131
120
253,537
113,741
NXF-0403N-CS2TS-H6
157
144
301,249
134,090
NXF-0403N-CS2TT-H1
27
12
52,706
24,402
NXF-0403N-CS2TT-H2
53
24
104,413
47,961
NXF-0403N-CS2TT-H3
79
36
155,120
70,693
NXF-0403N-CS2TT-H4
105
48
204,828
92,614
NXF-0403N-CS2TT-H5
131
60
253,537
113,741
NXF-0403N-CS2TT-H6
157
72
301,249
134,090
NXF-0603N-CS2TS-J1
39
36
86,654
31,244
NXF-0603N-CS2TS-J2
78
72
170,307
60,537
NXF-0603N-CS2TS-J3
117
108
250,992
87,955
NXF-0603N-CS2TS-J4
156
144
328,749
113,578
NXF-0603N-CS2TS-J5
165
180
403,623
137,484
NXF-0603N-CS2TS-J6
234
216
475,666
159,753
NXF-0603N-CS2TT-J1
39
18
86,654
31,244
NXF-0603N-CS2TT-J2
78
36
170,307
60,537
NXF-0603N-CS2TT-J3
117
54
250,992
87,955
NXF-0603N-CS2TT-J4
156
72
328,749
113,578
NXF-0603N-CS2TT-J5
165
90
403,623
137,484
NXF-0603N-CS2TT-J6
234
108
475,666
159,753
Figure 11.
Optional Positive Closure Dampers (PCDs)
Start-Up & Operation
Cold Weather Operation
hCore
®
Heat Transfer
Technology Freeze Protection
Positive Closure Dampers (PCDs) (Optional)
The amount of auxiliary heat required can be substantially reduced by the use of positive
closure dampers at the unit air discharge (see
Figure 11
). The dampers remain open as
long as the unit run state is active and remain closed whenever run state is inactive. The
heat loss data can be found in
Table 1.