9
9
• Ensure that Customer Input is set to “No”.
• Ensure that BMS On/Off Control is set to “No”.
• Select desired “Operating Mode” (see Selecting Your Operating Mode on
page 50
for
details about which mode to select), set Run Authorize to On, and adjust setpoint
to desired leaving fluid temperature. Run Authorize may also be toggled by remote
contacts by others; see wiring diagram for details.
• Navigate to User Menu and press enter.
For Local Control without a Building Management System (BMS) Interface
Start-Up & Operation
Start-Up
Pre-Start-up Checks
Start-up
• Refer to “iPilot
®
Control System Appendix” on
page 45
for more information
including for controls connections.
• Anytime equipment operation is required, Run Enable must be turned On
either locally through the iPilot
®
Control System interface or remotely with a
signal by others. When positive closure dampers are included, the run state
commands the dampers to open (On) and close (Off).