Components
The iPilot
®
Control System contains the following components:
Solenoid Make-up Valve
Check the nameplate for correct catalog number, pressure, voltage, frequency, and service.
Ensure that the incoming water pressure does not exceed the valve rating. Solenoid make-
up valve should be inspected every six months. However, the interval between cleanings
will vary depending on water quality and service conditions. If the voltage to the solenoid
is correct, then sluggish valve operation, excessive noise or leakage will indicate that
cleaning is required. The valve is normally closed, but faulty valve operation may cause it
to fail either open or closed. Clean strainer at supply (by others) when inspecting the valve.
Figure 27.
Solenoid Make-up Valve
Leaving Process Fluid and Ambient Temperature Sensors
Temperature sensors are constructed of stainless steel and are well-suited for corrosive
environments. For accuracy of measurement, the sensors should be inspected every six
months and deposit buildup should be removed.
Figure 28.
Leaving Process Fluid Temperature Sensor
Figure 29.
Ambient Temperature Sensor
Detailed Component
Maintenance Procedures
DiamondClear
®
Design
Water Diverter
iPilot
®
Control System
Components