Press the Settings key
•
Press the scroll down key until the "Pre-bleed" is highlighted (Default is 1150 USiemens)
•
Recommended setting is same as bleed set point minus dead band (typically 50 USiemens)
•
Adjust value as required
•
Press the scroll down key until the "Bleed Lock out" is highlighted (Default is 1.00 Hour)
•
Adjust value as required
•
Validate
R3 Scale and Corrosion Inhibitor Dosing
Preprogrammed with default values by BAC, see "Default parameters and set points" on page 16
Enter the correct values with following procedure
Program the setting for each biocide dosing
•
The inhib R3 relay output will be highlighted
•
Press the Settings key
•
Press the scroll down key until the "Feed Duration" is highlighted (Default is 2 minutes)