Use the left/right and Higher/Lower arrow key to change value if required (default 1 liter / impulse)
•
Press the Confirm key to accept the change
Water meter
Outputs R1, R2 and R3
R1: Bleed valve
Preprogrammed with default values by BAC, see "Default parameters and set points" on page 16
Enter the correct bleed set point with following procedure:
Program the setting for each output
•
The Bleed R1 relay output will be highlighted
•
Press the Settings key
•
Press the scroll down key until the Setpoint is highlighted
•
Press the Enter key
•
Use the left/right Higher/Lower arrow key to change value if required (default is 1200)
•
Press the Confirm key to accept the change
R2: Bio Timer
Preprogrammed with default values by BAC, see "Default parameters and set points" on page 16
Enter the correct values with following procedures:
The Bio Timer R2 relay output will be highlighted