3 General Description
12
DHV0078 b2 EN
©
b2 electronic
GmbH
3
General Description
3.1
Technical Specifications
Characteristic
1
HVA30-5
HVA34
HVA60
Article number
SH5004
SH5006
SH5014
Input supply voltage
110-240 V; 50/60 Hz; ± 10%
Input supply power
1.5 kVA
400 VA
1.5 kVA
max. output
voltage
VLF sine wave
23 kV
rms
33 kV
peak
24 kV
rms
34 kV
peak
44 kV
rms
62 kV
peak
VLF square wave
30 kV
34 kV
60 kV
DC [+/-]
30 kV
34 kV
60 kV
resolution: 0.1 kV, accuracy: ± 1%
max. output current
60 mA
rms
10 mA
rms
26 mA
rms
resolution: 1 µA, accuracy: ± 1%
Resistance range
0.1 MΩ….5 GΩ
Output frequency
0.01 Hz-0.1 Hz in steps of 0.01 Hz (default 0.1 Hz) –
auto frequency selection
Sheath test
max. test voltage: 10 kV, duration: 1 min-15 min
trip current: 0.1 mA-5.0 mA
Sheath fault location mode
2
max. test voltage: 10 kV, duration: 1 min-60 min
pulse/period: 1:3 / 4 s, 1:5 / 4 s, 1:5 / 6 s, 1:9 / 6 s
Frequency optimization
Yes
Output load
capacity
at 0.1 Hz
3.8 µF
0.5 µF
1 µF
at reduced
frequency/voltage
15 µF
12 µF
10 µF
Metering
voltage and current (true rms and/or peak),
capacitance, resistance, time, flashover voltage
Output duty
Continuous! No thermal limitation for operating time.
Test modes
manual & automatic
Output modes
AC (VLF) symmetrical and load independent across full range,
DC (plus or negative polarity), burn/fault condition or
fault trip mode, jacket/sheath testing
Safety
Dual discharge
device (internal)
3
50 Hz-12 kV feedback protection/
dual discharge device (internal)
Computer interface
RS232 & USB flash memory module
Record storage
Built-in memory: up to 50 reports, 40 test sequences
USB memory flash drive: unlimited
PC software [included]
b2 ControlCenter for Windows
Weight
45 kg
19.5 kg
57 kg
Dimensions
4
(mm) L x W x H
450 x 340 x 520
430 x 250 x 360
450 x 340 x 520
Environment
Storage temperature
-25°C to 70°C
Operation temperature
-10°C to 50°C
Humidity
5-85% non-condensing
Содержание HVA34
Страница 2: ...1 Introduction 2 DHV0078 b2 EN b2 electronic GmbH...
Страница 11: ...2 Safety b2 electronic GmbH DHV0078 b2 EN 11...
Страница 22: ...4 Design and Construction 22 DHV0078 b2 EN b2 electronic GmbH Switches and controls Front panel HVA34...
Страница 33: ...5 Test Procedure b2 electronic GmbH DHV0078 b2 EN 33 Connection diagram vacuum bottle test...
Страница 47: ...5 Test Procedure b2 electronic GmbH DHV0078 b2 EN 47 5 5 Discharge Status...
Страница 62: ...11 Declaration of Conformity 62 DHV0078 b2 EN b2 electronic GmbH 11 Declaration of Conformity HVA34...
Страница 63: ...11 Declaration of Conformity b2 electronic GmbH DHV0078 b2 EN 63 HVA30 5...
Страница 64: ...11 Declaration of Conformity 64 DHV0078 b2 EN b2 electronic GmbH HVA30 7 HVA40 5 HVA54 3...
Страница 65: ...11 Declaration of Conformity b2 electronic GmbH DHV0078 b2 EN 65 HVA54 5...
Страница 66: ...11 Declaration of Conformity 66 DHV0078 b2 EN b2 electronic GmbH HVA60...
Страница 67: ...11 Declaration of Conformity b2 electronic GmbH DHV0078 b2 EN 67 HVA68 2...
Страница 68: ...11 Declaration of Conformity 68 DHV0078 b2 EN b2 electronic GmbH HVA90 HVA94...
Страница 69: ...11 Declaration of Conformity b2 electronic GmbH DHV0078 b2 EN 69 HVA120...