![Azbil KFDB Скачать руководство пользователя страница 37](http://html1.mh-extra.com/html/azbil/kfdb/kfdb_user-manual_3042624037.webp)
31
Chapter 7. MAINTENANCE
Fig. 7-1. Points To Be Serviced For Maintenance
7-1. Periodical Inspection
(1) Check the air pipes and joints for leak.
(2) Check the air supply line drain, filter, compressor, air cleaner/drier, and tanks.
(3) Check the instrument filters and restrictions for stains. Replace the stained filters. Clean
the dirty restrictions using a needle wire of 0.12 mm diameter.
7-2. Controller Unit
(1) Turn off the air supply and remove the deviation link.
(2) Remove the four screws of the base, take out the controller unit, and clean the nozzle.
(3) Install the controller unit following the removing procedure in the reverse order. Adjust
the controller. Make sure that the O-rings are installed. Fix the controller securely with the
four screws and confirm that there is no air leak.