AB-6439
8
20 60 20
92
(60)
Duct
Infilex ZM
Duct
(60)
Duct
(122.5)*
1
(132.
5)*
1
65 75
(45)
35
140
35 (4
5)
DIN rail mounting bracket
(for bilateral sides)
Part No. 83104567-001
DIN rail position is shifted
5 mm downward from the
center of Infilex ZM.
DIN rail
Infilex ZM
DIN rail
Hook
Holder
Infilex ZM
Mounting Dimensions
DIN rail mounting
Mount and fix Infilex ZM on DIN rail so that it does not fall from the DIN rail.
Fasten the bilateral sides of Infilex ZM with two DIN rail mounting brackets (Part No. 83104567-001, separate order is required).
Notes:
1 Pitch between upper/lower duct and DIN rail.
2 Hatched area shows the maintenance clearance.
Figure 6. Mounting dimensions: DIN rail mounting (mm)
Direct screw-mounting
When Infilex ZM is mounted with screws, the screw tab (Part No. 83165861-001) is required.
Mount and fix Infilex ZM on the wall with two M4
8 screws.
Lengthwise mounting
Incorrect mounting:
Crosswise*
2
(face-up)
Notes:
1 Hatched are shows the maintenance space.
2 Do not mount Infilex ZM in crosswise (face-up) direction. Do not mount it with the surface plate facing upward or downward, either.
Figure 7. Mounting dimensions: Direct screw mounting (mm)
DIN rail holder
Pull out the DIN rail holder.
Screw tab
Part No. 83165861-001
To attach the screw tab,
insert the screw tab into
the slit provided on the
rear side of Infilex ZM.
Screw tab
Rear
side
35
140
35
154
20 60 20
*1
Infilex ZM
Vertical direction
Infilex ZM