Wiring specifications
Item Wiring
Wiring
length
Condition
Power supply
JIS
IV2.0 mm
2
or JIS CVV 2.0 mm
2
or greater
Ground
JIS IV 2.0 mm
2
or JIS CVV 2.0 mm
2
or greater
Ground resistance: 100
or lower
NC-bus
JCS IPEV-S 0.9 mm
2
500
m
SC-bus
LAN cable compliant with EIA/TIA-568 category 3 or over
1000 m
Notes:
As M3 screw terminal block is used for power supply and ground, crimped terminal lug is required for the cable end.
Since a quick-fit screwless terminal block is provided for NC-bus connection, the wires can be connected only by stripping the sheath.
Sheath stripped length: 8 mm (Pin terminal cannot be used.)
Organize the cables with cable binding bands so as not to hide LED, Data Setter connector,
►
mark, switch, battery holder, or tag.
JIS: Japanese Industrial Standards
JCS: Japanese Electric Wire and Cable Makers’ Association
CE Marking Conformity
This product must be installed in a panel cabinet. Besides, the product in the panel cabinet must be out of reach of unauthorized
people who are not well-trained for electric facilities.
This product complies with the following Electromagnetic Compatibility (EMC) and the Low Voltage Directive (LVD).
EMC: EN61326-1 Class A, Table 2 (For use in an industrial electromagnetic environment)
LVD : EN61010-1 Overvoltage category II
Pollution degree 2
Input/Output Terminal Arrangement
Figure 2. Input/output and terminal arrangement example
SC-bus
RJ-45 modular jack
100 V AC to 240 V AC
NC-bus Line A
1
2
3
4
TX IN
TX OUT
TX IN
TX Out
(+)
(-)
Shield
Shield
(+)
(-)
(+)
(-)
5
6
7
8
9
10
11
12
NC-bus Line B