AB-6439
7
Parts Identification
Figure 4. Parts identification
Table 1. Indication and operation of operating status LED
LED indication
LED operation
Data transmitting
NC-bus TX LED: flashing
Data receiving
NC-bus RX LED: flashing
Data transmitting
SC-bus TX LED: flashing
Data receiving
SC-bus RX LED: flashing
Major failure / initializing
ERR1: ON
Minor failure / initializing
ERR2: ON
Connections of Data Setter (H-MMI)
1) Connection of Data Setter Model QY5111A
No conversion cable is required. Directly insert the male connector of the Data Setter into the female connector provided on
the Infilex ZM main unit.
At this time, hold the male connector with the
◄
mark facing left and insert it as the mark points to the
►
mark on the Infilex
ZM main unit.
2) Connection of Data Setter Model QY7211A
Convert the D-SUB connector to the mini DIN connector with the conversion cable (Part No. 83104995-001).
At this time, hold the male connector with the
◄
mark facing left and insert it as the mark points to the
►
mark on the Infilex
ZM main unit.
Figure 5. Connecting Data Setter
Insert the connector as
the two arrows point to
each other.
Power switch
LED for power
ON/OFF
Battery holder
LED for
operating status
S1 switch*
Connector (female)
for Data Setter
Do not press S1 switch.
DIN rail
mounting
hook
8mm
Stripping Length
BATT.
S
-
+
S
~
NC-bus
NC-bus
+
-
CN1
O
3
2
1
POWER
I
SC-bus
ERR1
ERR2
S1
H-MMI
RX
Tx
RX
Tx
6
5
7
8
9
10
SC-bus
E
4
12
11
-
+