background image

E4

 

l

Size of monitoring pipe

For the detector to receive the optimal amount of UV radiation, 

its field of vision should be as wide as possible. To that end, do 

the following:

(1)  Use the widest monitoring pipe possible, at least 50 to 

80 A, and connect the AUD100/110 with a reducer. 

(2)  Make the monitoring pipe as short as possible. (However, 

remember that the ambient temperature of the 

AUD100/110 should not exceed 120 °C.)

 

l

Mounting space

Leave sufficient space to allow easy maintenance and 

inspection.

 

„

Adjustment and inspection

After wiring, do the following checks.
(1)  Using the FSP136A100 Analog Flame Meter

• 

If measuring the flame current:  

Insert the flame current measurement plug of the 

FSP136A100 into the flame current measurement jack of the 

burner controller.

• 

If measuring the flame voltage:  

Connect the red and black flame voltage measurement 

probes from the FSP136A100 to the + and - flame voltage 

output terminals respectively on the burner controller. 

(2)  Check the operation of the AUD100/110 by exposing the 

AUD15 to a lighter flame or to ultraviolet rays from an ultra-

violet lamp.

  Handling Precautions

• 

Before using an open flame, check that there is no flam-
mable gas in the vicinity.

(3)  Mount the AUD100/110 on the monitoring pipe temporarily.
(4)  Light the burner.
(5)  To determine the optimal monitoring position, measure the 

flame current/voltage with the FSP136A100 analog flame 

meter while slowly moving the monitoring pipe. Select 

the position with the highest possible stable flame current 

and voltage which is also within the specified range for the 

burner controller.  

Fluctuation of the reading within the width of the indicator 

needle is OK. 

For the specified flame current and voltage range for the 

burner controller, see the manual of the burner controller. 

 

l

Pilot burner turndown test

WARNING

If the flame detector is set so that it detects a pilot 

flame that is too small to ignite the main flame, the 

AUD100/110 will not be able to recognize (for example) 

a flame failure in the main burner. In this case fuel would 

continue to be supplied, causing a serious explosion haz-

ard. To prevent this, be sure to do the pilot turndown test 

carefully.
If it is necessary to do this test repeatedly, completely 

shut down all equipment each time the test is finished, 

and completely discharge unburned gas or oil that has 

accumulated in the ducts and combustion chamber. If un-

burned gas or oil is not expelled completely, an explosion 

may occur.

CAUTION

This test should be done only by a trained and experi-

enced professional.

The purpose of this test is to determine whether, under the least 

favorable conditions of gas pressure and air pressure, a pilot flame 

detected by the flame detector will reliably light the main burner. For 

the procedure of the pilot turndown test, follow the instructions in 

the burner controller manual or equipment manufacturer manual.

 

l

Ignition spark response test

WARNING

Make sure that this device does not detect ultraviolet 

rays other than those of the burner flame. If it does, a 

false flame signal will endanger combustion safety. 

Make sure that the flame relay (normally relay 2K) is not af-

fected by the spark generated by the ignition transformer. 
This test examines whether this device responds to ultraviolet 

rays of the ignition transformer.
For the procedure of the ignition spark response test, follow 

the instructions in the burner controller manual or equipment 

manufacturer manual.

 

„

Final mounting of the monitoring pipe

• 

When the equipment is operating properly with the specified 

flame voltage output after all adjustments have been completed, 

turn OFF the power to the equipment, remove the AUD15 and 

AUD100/110, and weld the monitoring pipe permanently.

• 

Mount the AUD15 and AUD100/110 on the monitoring pipe 

and do all of the wiring.

• 

As a guideline for mounting, tighten the nut 1 quarter turn 

after contacting the edge of the mounting pipe and the packing 

for the nut.  Then, check the tightness, include the welding part 

of the mounting pipe using a tightness test, etc.

 

„

Label attachment

Attach the effective operation time label to a place where it can be 

seen easily. Attach the expiration date label to the socket.

 

„

Final inspection

To ensure proper burner control, do a trial run of at least one 

complete operation cycle of the combustion equipment to verify 

that all control operations function correctly.

MAINTENANCE AND INSPECTION

CAUTION

The effective life of the AUD15 is a total of 25,000 

hours of use or 5 years (from   the date indicated by 

the date code on the model No. label). 

Be sure to replace it with a new Tube Unit within this 

period. 

Note.  The effective life is the time when UV sensor de-

tects a flame.

Take special care in handling the AUD15 to avoid im-

pact and shock.
When transporting or storing the AUD15, be sure to 

put it in a secure packing box.

 

„

  Maintenance and inspection work for the model 
AUD15 and model AUD100/110

 

l

Flame failure test

To check that the flame safeguard control device works prop-

erly, do the flame failure test regularly.  
During normal burner combustion, block the monitoring pipe 

window so that there is no flame signal, or else cut off the fuel 

at the source to extinguish the burner flame.  Check that the 

flame failure is detected and that the main valve and pilot valve 

are closed.

 

l

Flame signal check

Regularly check the flame signal from the burner controller 

that is used for batch operation. For the method of checking, 

see the user’s manual for the burner controller.

Содержание AUD100 Series

Страница 1: ...15 AUD100 110 AUD15 AUD15 25 000 5 UV UV AUD100 110 AUD15 AUD100 AUD15 AUD100 AUD110 2 AUD100 110 AUD100C100 UV AUD15 AUD100C1000 A15 UV AUD15 AUD110C100 UV AUD15 AUD110C1000 A15 UV AUD15 0 D T AUD110...

Страница 2: ...efore using and use it correctly Please read instructions carefully 9735 001 02 25 000 5 AUD15 X X 1371 J6 AUD100 110 AUD15 AUD100 110 AUD15 AUD100 110 AUD15 1 3 2 AUD100 F G AUD110 AUD110 F F G G AUD...

Страница 3: ...M3 5 7 3 7 mm 0 98 N m F G AUD110 AUD15 100k F G DC G F F DC160 220 V G DC160 220 V DC F G AUD100 1 3 F G 1 AUD15 50 80A AUD100 110 AUD100 110 AUD100 110 AUD100 110 AUD100 110 AUD100 110 AUD100 110 F...

Страница 4: ...AUD100 110 50 80A AUD100 110 AUD100 110 120 FSP136A100 FSP136A FSP136A AUD15 AUD100 110 AUD100 110 FSP136A100 AUD100 110 2K AUD100 110 AUD15 AUD100 110 1 4 1 25 000 5 UV UV AUD15 AUD15 AUD100 110 AUD...

Страница 5: ...AUD15 AUD100 110 AUD15 AUD100 110 AUD15 J2 AUD100 110 AUD100 G1 2 AUD110 AUD100 110 20 120 40 90 RH AUD100 AUD110 120 g AUD15 140 g 120 g AUD15 140 g DC500 V 50 M AUD15 IP65 JIS C 0920 IEC 60529 35 kP...

Страница 6: ...10 10 V 2010 2020 Azbil Corporation All Rights Reserved AUD110C100 AUD15 mm 60 140 90 40 64 76 G1 2 52 G1 AUD15 F G M3 5 AUD100C100 AUD15 mm 105 55 64 41 G1 2 G1 40 24 1800 AUD15 AUD15C1000 81447479 0...

Страница 7: ...ination with Azbil Corporation s burner controllers CAUTION Installation wiring maintenance inspection adjustment and the like of the AUD15 and AUD100 110 should be car ried out only by a trained and...

Страница 8: ...r chlorine ethylene compounds acids or corrosive gases Prolonged vibration If gas cannot be allowed to leak out of the furnace through the monitoring pipe take appropriate counter measures A sealed ad...

Страница 9: ...pipe 50 to 80 A Pilot burner Main burner AUD100 110 zMounting angle Mount the AUD100 110 so that it monitors the burner at an angle from above Handling Precautions If the AUD100 110 monitors from bel...

Страница 10: ...and air pressure a pilot flame detected by the flame detector will reliably light the main burner For the procedure of the pilot turndown test follow the instructions in the burner controller manual o...

Страница 11: ...h the light receiving glass surface zHow to replace the nut packing If the nut packing is damaged replace it according to the pro cedure below 1 Remove the AUD100 110 from the monitoring pipe 2 Hold t...

Страница 12: ...ion s burner controllers REPLACEMENT OPTIONAL PARTS sold separately Model No Description AUD15C1000 Tube Unit Ultraviolet photoelectric tube 81447479 001 Nut Packing 81403159 Seal adapter FSP100R15000...

Отзывы: