AB-7043 

Items to be displayed on LCD 

Analog  values  such  as  pressure,  flow,  and  temperature  are  displayed  on  the  LCD.  Setting  buttons  set/change  various 
parameters and display error description (when an error occurs). Be sure to enable the parameter setting (Parameter 60) before 
changing any parameters. For details, see 

AB-7044 Instruction Manual of A

 Modbus

 Protocol / Standalone 

Model.

 

 

 Analog values display screen 

Analog values display screen appears on the LCD when you turn on the Display Panel. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 
 

Figure 4.  Analog values display screen 

 

Display area 

Description 

Display range 

Unit 

 

Item 

Display Panel connected to: 

Range 

Pvin 

Valve inlet pressure 

Model FVY5130/FVY5140/FVY5150  0.000 to 1.100 

MPa 

0 to 1100 

kPa *

1

 

Model FVY5137/FVY5147/FVY5157  0.000 to 1.800 

MPa 

0 to 1800 

kPa *

1

 

Model FVY513E/FVY514E 

0.000 to 2.200 

MPa 

0 to 2200 

kPa *

1

 

Pvout 

Valve outlet pressure 

Model FVY5130/FVY5140/FVY5150  0.000 to 1.100 

MPa 

0 to 1100 

kPa *

1

 

Model FVY5137/FVY5147/FVY5157  0.000 to 1.800 

MPa 

0 to 1800 

kPa *

1

 

Model FVY513E/FVY514E 

0.000 to 2.200 

MPa 

0 to 2200 

kPa *

1

 

Actual flow 

0 to 9999 

m

3

/h or l/min *

2

 

T

1

 

Coil inlet temperature 

-10.0 to 99.9 

°C 

T

2

 

Coil outlet temperature 

-10.0 to 99.9 

°C 

Opening 

Valve position indicated in a bar graph 

0 to 100 (with every 10 % increment) 

Flowrate 

Flow indicated in a bar graph 

0 to 100 (with every 10 % increment) 

Error occurred ([E] flashes.) 

 

 

H C 

AHU operation mode ([H]: Heat / [C]: Cool) 

 

 

Notes: 
 *1  The unit of the valve inlet and outlet pressure is selectable between 'MPa' and 'kPa' by setting on the Display Panel (Model QY5010S). If you 

select 'kPa,' put the 'kPa' unit stickers supplied with the Display Panel. 

 *2  The unit of the actual flow is selectable between 'm

3

/h' and 'l/min' by setting on the Display Panel (Model QY5010S). The selected unit is 

indicated with [

] mark on the display. 

 

Setting buttons 

Function 

[

] Cursor button 

Not used in  the analog values display screen. 

[

] Down button 

Press this button to switch to the error display screen when the error indicator [E] flashes. 

[

] Up button 

Press this button to switch to the error display screen when the error indicator [E] flashes. 

[ENT] Enter button 

Press and hold this button to switch to the parameter setting screen. 

Heat/Cool operation mode

indicator

Display area 1 

Enter button 

Error indicator

Display area 2 

Display area 3 

Display area 4 

Display area 5 

Up button 
Down button 

Cursor button 

Valve position in bar graph

Flow rate in bar graph

Содержание ACTIVAL+

Страница 1: ...ve position at one time Installable 50 m away from Model FVY513_J FVY514_J FVY515_J Display panel is connected to Model FVY513_J FVY514_J FVY515_J with JIS VCTF cable 0 3 mm2 4 cores and max cable len...

Страница 2: ...ssembly is prohibited Instructs users to carry out a specific obligatory action to prevent possible danger The symbol inside d graphically indicates the actual action to be carried out For example the...

Страница 3: ...Coil inlet temperature C T2 Coil outlet temperature C HC Heat Cool E Error Opening Actual valve position in bar graph Flowrate Actual flow rate in bar graph Communication Transmission system AP bus RS...

Страница 4: ...igure 1 Outside dimensions mm Mounting dimensions of the base plate Figure 2 Mounting dimensions of the base plate mm 96 24 5 96 Base plate Case 48 48 33 15 66 15 51 5 Mounting holes Cable conduit Hoo...

Страница 5: ...AB 7043 5 Parts Identification Figure 3 Parts identification Hook to remove the case from the base plate Base plate Case Face plate Insertion guide female LCD Insertion guide male...

Страница 6: ...2 4 T1 Coil inlet temperature 10 0 to 99 9 C 5 T2 Coil outlet temperature 10 0 to 99 9 C Opening Valve position indicated in a bar graph 0 to 100 with every 10 increment Flowrate Flow indicated in a...

Страница 7: ...s button to go back to the analog values display screen Note No button operation for continuous 10 minutes on the parameter setting screen will automatically switch from the parameter setting screen t...

Страница 8: ...ripped lead wires to each terminal Terminals arrangement Figure 7 Sheath strip length Terminal number Type Lead wire color 1 12 V DC Red RED 2 0 V Black BLK 3 AP bus White WHT 4 AP bus Green GRN Note...

Страница 9: ...ate terminals out of the base plate through the base plate conduit on the bottom right and mount the base plate on the mounting location with the two M4 tapping screws accessory of Display Panel Figur...

Страница 10: ...is generally installed on a visible position such as on a wall in a machine room or on a control panel cabinet However it may possibly be installed outdoors or in a ceiling In such a case install the...

Страница 11: ...VY513_J FVY514_J FVY515_J To connect the cable to Model FVY513_J FVY514_J FVY515_J refer to Specification Installation of Model FVY513_J FVY514_J FVY515_J AB 7408 ACTIVAL Modbus Protocol Model PN16 EN...

Страница 12: ...cations are subject to change without notice Building Systems Company http www azbil com Rev 6 0 Mar 2018 AB 7043 J AI 7043 Rev 2 2 12 This product complies with the following harmonised standards of...