4)  Arrange the cable connected to Display Panel. 

Cautions for arranging the cable: 

 

Do not pull the cable. 

 

To prevent water from flowing down to Display Panel through the cable, let the cable sag, as Fig. 12 shows. 

 

When installing Display Panel on an AHU side plate, seal the wiring hole on the AHU side plate, as Fig. 12 shows. 

 

Damp or dew condensation may damage the Display Panel, otherwise. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 12.  Cable arrangement 

 

5)  Film is attached to the front surface (face plate) of Display Panel for protection before shipment. Remove the film before 

activating Display Panel. 

 

6)  Display Panel is generally installed on a visible position such as on a wall in a machine room or on a control panel cabinet. 

However, it may possibly be installed outdoors or in a ceiling. In such a case, install the Display Panel as shown in Figs. 13 
and 14. Consider the conditions and requirements of your Display Panel installation and decide the location. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 13.  Display Panel installed outdoors (in a rainproof box) 

Display Panel 

Display Panel 

Sealing material 

Sealing material 

Cable 
Let the cable sag. 

Cable 
Let the cable sag. 

Cable led out of the rear side of Display Panel 

Cable led through the conduit of Display Panel 

50 mm stanchion 

Display Panel

in a protection box

Display Panel 

in a protection box 

directly on a wall 

50 mm stanchion 

Display Panel 
in a plastic box 
(commercially available) 

Содержание ACTIVAL+

Страница 1: ...ve position at one time Installable 50 m away from Model FVY513_J FVY514_J FVY515_J Display panel is connected to Model FVY513_J FVY514_J FVY515_J with JIS VCTF cable 0 3 mm2 4 cores and max cable len...

Страница 2: ...ssembly is prohibited Instructs users to carry out a specific obligatory action to prevent possible danger The symbol inside d graphically indicates the actual action to be carried out For example the...

Страница 3: ...Coil inlet temperature C T2 Coil outlet temperature C HC Heat Cool E Error Opening Actual valve position in bar graph Flowrate Actual flow rate in bar graph Communication Transmission system AP bus RS...

Страница 4: ...igure 1 Outside dimensions mm Mounting dimensions of the base plate Figure 2 Mounting dimensions of the base plate mm 96 24 5 96 Base plate Case 48 48 33 15 66 15 51 5 Mounting holes Cable conduit Hoo...

Страница 5: ...AB 7043 5 Parts Identification Figure 3 Parts identification Hook to remove the case from the base plate Base plate Case Face plate Insertion guide female LCD Insertion guide male...

Страница 6: ...2 4 T1 Coil inlet temperature 10 0 to 99 9 C 5 T2 Coil outlet temperature 10 0 to 99 9 C Opening Valve position indicated in a bar graph 0 to 100 with every 10 increment Flowrate Flow indicated in a...

Страница 7: ...s button to go back to the analog values display screen Note No button operation for continuous 10 minutes on the parameter setting screen will automatically switch from the parameter setting screen t...

Страница 8: ...ripped lead wires to each terminal Terminals arrangement Figure 7 Sheath strip length Terminal number Type Lead wire color 1 12 V DC Red RED 2 0 V Black BLK 3 AP bus White WHT 4 AP bus Green GRN Note...

Страница 9: ...ate terminals out of the base plate through the base plate conduit on the bottom right and mount the base plate on the mounting location with the two M4 tapping screws accessory of Display Panel Figur...

Страница 10: ...is generally installed on a visible position such as on a wall in a machine room or on a control panel cabinet However it may possibly be installed outdoors or in a ceiling In such a case install the...

Страница 11: ...VY513_J FVY514_J FVY515_J To connect the cable to Model FVY513_J FVY514_J FVY515_J refer to Specification Installation of Model FVY513_J FVY514_J FVY515_J AB 7408 ACTIVAL Modbus Protocol Model PN16 EN...

Страница 12: ...cations are subject to change without notice Building Systems Company http www azbil com Rev 6 0 Mar 2018 AB 7043 J AI 7043 Rev 2 2 12 This product complies with the following harmonised standards of...

Отзывы: