Specifications/Instructions 

Display Panel for 

 

Modbus™ Protocol / Standalone Model 

 
General 

Display Panel Model QY5010S1000 is the data indicator for 
ACTIVAL  +

.  Display  Panel  displays  data  measured  by 

Model FVY513_J/ FVY514_J/FVY515_J (flow pressure, flow 
temperature, flow) and valve position. 
Besides, the setting buttons on the Display Panel allow you 
to set and change various data. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Features 

 

Multiple data in a single display: 
You can check flow temperature of AHU inlet/outlet, flow 
pressure  of  valve  inlet/outlet,  and  flow  measured  by 
Model  FVY513_J/FVY514_J/FVY515_J  and  the  valve 
position at one time. 

 

Installable 50 m away from Model FVY513_J/FVY514_J/ 
FVY515_J: 
Display  panel  is  connected  to  Model  FVY513_J/ 
FVY514_J/FVY515_J with JIS* VCTF cable (0.3 mm

2

 

 

4 cores), and max. cable length is 50 m. 

   *  JIS: Japanese Industrial Standards 

 

Continuous display: 
Display  Panel  displays  data  all  the  time.  You  can  thus 
check flow conditions and valve position at any time. 

 

Compact and lightweight: 
Small  and  light  body  facilitates  installation  on  an  AHU 
panel or inside a control panel cabinet. 

 

 

 

Easy wiring: 
Since Display Panel main unit is connected to the base 
plate with the connector inside, wiring to Display Panel is 
complete only by connecting the wires to the base plate. 

 

Parameter setting and error code check available: 
Display Panel  allows  you to  set parameters and check  
error codes of Model FVY513_J/FVY514_J/FVY515_J. 

 

Содержание ACTIVAL+

Страница 1: ...ve position at one time Installable 50 m away from Model FVY513_J FVY514_J FVY515_J Display panel is connected to Model FVY513_J FVY514_J FVY515_J with JIS VCTF cable 0 3 mm2 4 cores and max cable len...

Страница 2: ...ssembly is prohibited Instructs users to carry out a specific obligatory action to prevent possible danger The symbol inside d graphically indicates the actual action to be carried out For example the...

Страница 3: ...Coil inlet temperature C T2 Coil outlet temperature C HC Heat Cool E Error Opening Actual valve position in bar graph Flowrate Actual flow rate in bar graph Communication Transmission system AP bus RS...

Страница 4: ...igure 1 Outside dimensions mm Mounting dimensions of the base plate Figure 2 Mounting dimensions of the base plate mm 96 24 5 96 Base plate Case 48 48 33 15 66 15 51 5 Mounting holes Cable conduit Hoo...

Страница 5: ...AB 7043 5 Parts Identification Figure 3 Parts identification Hook to remove the case from the base plate Base plate Case Face plate Insertion guide female LCD Insertion guide male...

Страница 6: ...2 4 T1 Coil inlet temperature 10 0 to 99 9 C 5 T2 Coil outlet temperature 10 0 to 99 9 C Opening Valve position indicated in a bar graph 0 to 100 with every 10 increment Flowrate Flow indicated in a...

Страница 7: ...s button to go back to the analog values display screen Note No button operation for continuous 10 minutes on the parameter setting screen will automatically switch from the parameter setting screen t...

Страница 8: ...ripped lead wires to each terminal Terminals arrangement Figure 7 Sheath strip length Terminal number Type Lead wire color 1 12 V DC Red RED 2 0 V Black BLK 3 AP bus White WHT 4 AP bus Green GRN Note...

Страница 9: ...ate terminals out of the base plate through the base plate conduit on the bottom right and mount the base plate on the mounting location with the two M4 tapping screws accessory of Display Panel Figur...

Страница 10: ...is generally installed on a visible position such as on a wall in a machine room or on a control panel cabinet However it may possibly be installed outdoors or in a ceiling In such a case install the...

Страница 11: ...VY513_J FVY514_J FVY515_J To connect the cable to Model FVY513_J FVY514_J FVY515_J refer to Specification Installation of Model FVY513_J FVY514_J FVY515_J AB 7408 ACTIVAL Modbus Protocol Model PN16 EN...

Страница 12: ...cations are subject to change without notice Building Systems Company http www azbil com Rev 6 0 Mar 2018 AB 7043 J AI 7043 Rev 2 2 12 This product complies with the following harmonised standards of...

Отзывы: