ACTIVAL™ 

Two-way Ball Valve with Threaded-end Connection 

 

General 

ACTIVAL™ Model VY5302B is a two-way ball valve with 
threaded-end connection (ASME B1.20.1). It proportionally 
controls chilled/hot water for HVAC applications. 

Model VY5302B has bronze valve body, stainless-steel ball 
and stem, and the components exposed to process fluid are 
made of other corrosion resistant materials.  

Cv value and size variation of Model VY5302B are best 
suited to HVAC control. 

Model VY5302B is used in combination with the actuator 
Model MY53X0A. Regarding the detailed information on the 
actuator, refer to: 

Specifications/Instructions of ACTIVAL Model MY53X0A

 

HVAC: Heating, ventilation, and air conditioning 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Features 

  Compact and lightweight 

Valve can be installed in a restricted space such as 
inside of a compact AHU*. 

  Bronze valve body applicable to 230 psig** 

  Easy assembly with Model MY53X0A actuator using no 

tool, and no adjustment required 

  Equal percentage flow characteristic 

*  AHU: Air handling unit 
**  This product was designed and manufactured conforming to  

the ISO (International Organization for Standardization, PN16). 

 
Model Numbers 

Base model 

number 

Material 

 

Size/

Cv 

Description 

VY53   

 

Two-way 

valve 

with 

threaded-end connection

 0 

 

 

Bronze 

  

2B00 

 

Fixed 

 

 

 

11 

 1/2” / 2.5 Cv 

 

 

 

12 

 1/2” / 4 Cv 

 

 

 

22 

 3/4” / 6.3 Cv 

 

 

 

23 

    1” / 10 Cv 

  

 

31 

1

1

/

4

” / 16 Cv  

  

 

41 

1

1

/

2

” / 25 Cv 

  

 

42 

1

1

/

2

” / 40 Cv 

 

Dimensions and Maintenance Clearance 

 

Model No. 

Dimensions 

DN

NPT 

(in)

Unit L 

VY5302B0011

15

1/2

in 2.48  1.87  1.06 

mm 63  47.5 

27 

VY5302B0012

15

1/2

in 2.48  1.87  1.06 

mm 63  47.5 

27 

VY5302B0022

20

3/4

in 2.83  1.97  1.3 

mm 72 

50 

33 

VY5302B0023

25

in 3.35  2.11  1.61 

mm 85  53.5 

41 

VY5302B0031

32

in 3.88  2.7  1.97 

mm 98.5  68.5 

50 

VY5302B0041

40

in 4.27  2.83  2.2 

mm 108.5 

72 

56 

VY5302B0042

40

in 4.27  2.83  2.2 

mm 108.5 

72 

56 

 

Figure 1.  Dimensions and maintenance clearance 

(MY53)

Содержание ACTIVAL VY5302B

Страница 1: ...ed space such as inside of a compact AHU Bronze valve body applicable to 230 psig Easy assembly with Model MY53X0A actuator using no tool and no adjustment required Equal percentage flow characteristic AHU Air handling unit This product was designed and manufactured conforming to the ISO International Organization for Standardization PN16 Model Numbers Base model number Material Size Cv Descriptio...

Страница 2: ...tmosphere etc listed in the specifications Failure to do so might cause fire or device failure Use the product within its lifespan and avoid instrumentations that keep the product to operate excessively Continued use beyond the lifespan might cause fire or device failure Keep the products in package for storage Failure to do so might damage or stain the products Installation and wiring must be per...

Страница 3: ...Valve size Cv close off rating Model number Nominal size Cv Close off rating Inch DN VY5302B0011 1 2 15 2 5 145 psig VY5302B0012 1 2 15 4 145 psig VY5302B0022 3 4 20 6 3 145 psig VY5302B0023 1 25 10 145 psig VY5302B0031 1 1 4 32 16 72 psig VY5302B0041 1 1 2 40 25 72 psig VY5302B0042 1 1 2 40 40 72 psig Materials Body Cast bronze Cap Cast bronze Seat ring Carbon Reinforced PTFE Ball Cast stainless ...

Страница 4: ...ons Doing so might damage the product Do not excessively screw a pipe into the valve Doing so might damage or deform the inside of the valve causing leakage and malfunction Install the product so that no foreign objects remains inside the pipes Be sure to provide a strainer on the inflow side of the piping Flush the piping to remove the foreign objects after installation Foreign objects inside the...

Страница 5: ...the inflow outflow and bypass sides Also install a strainer with 40 or more meshes on the inflow side When installing the valve to pipes do not allow any object such as chips to get inside a pipe or valve Valve cannot fully closes or the valve seat may get damaged causing fluid leakage due to an foreign object jammed inside the valve When piping do not apply too much sealing material such as solid...

Страница 6: ...ositions of the actuator and the valve as follows referring to Fig 7 Actuator Indicator manual lever points at 100 fully open position Valve An arrow on the top of the stem points at 100 fully open position Align the hole on the side of the stem with the tip at the joint surface as a in Fig 7 shows Set the ACTIVAL actuator and valve in 100 position when changing the mounting position If the valve ...

Страница 7: ... direction at which the tip of the valve joint surface with the actuator points when the valve position is fully open See a in Fig 7 Figure 10 Valve stem pointing at 100 fully open position 4 Assemble Model MY53X0A actuator with the valve Engage 4 pins of the actuator with the mating holes on the valve joint surface 5 Move the lock lever to left end to lock Locked position is indicated with the gr...

Страница 8: ...ps halfway valve does not operate at all Conditions of the power applied and of the input signal applied to the actuator Wiring condition disconnected wires of the actuator Foreign substance jammed Check the power supply and the controller connected to Check the wiring Remove foreign substance by manually opening the valve Fluid leaks to the outside of the valve when the assembled actuator fully c...

Отзывы: