17
AB-7489-U
Table 2. Troubleshooting
Problem
Part to check
Action
Fluid leaks from the flange face.
Loosened flange bolts
Gasket on the flange face
Misaligned piping
Tighten the flange bolts.
Replace the gasket.
Redo piping.
Fluid leaks from the gland part.
Consult with our sales personnel.
Fluid leaks from the bonnet.
Loosened bolts
Tighten the bolts.
Valve does not operate smoothly /
valve stops halfway /
valve does not operate at all.
Conditions of the power applied and of the input
signal applied
Loosened terminals
Wiring condition / disconnected wires
Check the power supply and the controller
connected to.
Tighten the terminals.
Check the wiring.
Fluid leaks to the outside of the valve
when the ACTIVAL is in fully closed
position.
Actuator pointer not pointing to fully closed
position
Fully close the ACTIVAL.
The valve vibrates or produces an
abnormal noise.
Primary pressure condition
Differential pressure condition
Adjust the mounting position and change the
installation location.
The auxiliary switch does not operate.
Auxiliary switch (cam switch) condition
Loosened terminals
Wiring condition / disconnected wires
Redo the cam switch setting.
Tighten the terminals.
Check the wiring.
Valve hunting occurs.
Secondary pressure condition
Differential pressure condition
Control stability
Adjust the mounting position and change the
installation location.
Correct the control parameter setting of
controller.
Input signal disagrees with the feedback
output signal.
To completely shut off the valve, valve open and close (0-100% position) operation is controlled
by 10-90 % range of actuator voltage/current input signal. Input signal therefore disagrees with
the feedback signal, and this is not an error.
Disposal
Dispose of this product as industrial waste in accordance with your local regulations.
Do not reuse all or any part of the product.