background image

2

AB-7489-U

Safety Precautions 

Please read instructions carefully and use the 

product as specified in this manual. Be sure to keep 

this manual nearby for quick reference. 

Restrictions on Use

This product was developed, designed, and 

manufactured for general air conditioning use.
Do not use the product in a situation where human 

life may be at risk or for nuclear applications in 

radiation controlled areas. If you wish to use the 

product in a radiation controlled area, please 

contact Azbil Corporation.
Particularly when the product is used in the 

following applications where safety is required, 

implementation of fail-safe design, redundant 

design, regular maintenance, etc., should be 

considered in order to use the product safely and 

reliably. 
• Safety devices for protecting the human body
•  Start/stop control devices for transportation 

machines

• Aeronautical/aerospace machines 
For system design, application design, instructions 

for use, or product applications, please contact 

Azbil Corporation.
Azbil Corporation bears no responsibility for any 

result, or lack of result, deriving from the 

customer’s use of the product.

Recommended Design Life

It is recommended that this product be used within 

the recommended design life.
The recommended design life is the period during 

which you can use the product safely and reliably 

based on the design specifications. 
If the product is used beyond this period, its failure 

ratio may increase due to time-related 

deterioration of parts, etc. 
The recommended design life during which the 

product can operate reliably with the lowest failure 

ratio and least deterioration over time is estimated 

scientifically based on acceleration tests, 

endurance tests, etc., taking into consideration the 

operating environment, conditions, and frequency 

of use as basic parameters. 
The recommended design life of this product is 10 

years.
The recommended design life assumes that 

maintenance, such as replacement of the limited 

life parts, is carried out properly. 
Refer to the section on maintenance in this manual.

Warnings and Cautions

WARNING

Alerts users that improper handling 

may cause death or serious injury.

CAUTION

Alerts users that improper handling 

may cause minor injury or material 

loss.

Signs

Notifies users that specific actions are 

prohibited to prevent possible danger. The 

symbol inside 

 graphically indicates the 

prohibited action. (For example, the sign on 

the left means that disassembly is 

prohibited.)

Instructs users to carry out a specific 

obligatory action to prevent possible danger. 

The symbol inside 

 graphically indicates the 

actual action to be carried out. (For example, 

the sign on the left indicates general 

instructions.)

 

WARNING

When handling or transporting any heavy 

product (more than 39.7 lb (18 kg)), carefully 

move the product with a handtruck or the 

like, or with 2 or more people.

Careless lifting or accidental dropping of the 

product may result in injury or product 

damage.

 

CAUTION

Provide a circuit protector (e.g., a fuse or 

circuit breaker) for the power source.

Failure to do so may cause a short circuit 

leading to fire or device failure.

Do not freeze this product.

Doing so may damage the valve body and 

cause leakage.

When piping this product, be sure there is no 

foreign matter in the pipes.

If foreign matter remains in the pipes, the 

product may break down.

Install, wire, and use this product under the 

conditions specified by this manual.

Failure to do so may cause fire or device 

failure.

Use full face gaskets for flat face flanges.

Failure to do so may damage the flanges or 

cause leakage outside of the valve.

When installing this product, hold it in the proper 

position and securely fasten it to the pipes.

Excessive tightening or improper installation 

position may damage the valve.

Содержание ACTIVAL VY51 Series

Страница 1: ...lable 4 20 mA DC input 2 10 V DC input Valve for chilled hot water control and for steam control applicable to high differential pressure large Cv value high rangeability and low leakage Durable actua...

Страница 2: ...ency of use as basic parameters The recommended design life of this product is 10 years The recommended design life assumes that maintenance such as replacement of the limited life parts is carried ou...

Страница 3: ...e UL50E Type 4 Enclosure 2 Only the actuator is certified with the UL cUL above CAUTION After installation make sure no fluid leaks from the valve pipe connections Improper piping may cause fluid leak...

Страница 4: ...ristics Equal percentage Rangeability 100 1 Seat leakage Class IV 0 01 of rated Cv value Paint Gray Actuator to be combined Integrated with the valve Actuator specifications Item Specification Power s...

Страница 5: ...t must be avoided Outdoor Use the outdoor cover etc to be ordered separately Direct sunlight salt air corrosive gas flammable gas and organic solvent must be avoided Installation orientation Installab...

Страница 6: ...4 44 1 Figure 1 Dimensions and maintenance clearance Model VY51_FJ VY51_GJ Parts Identification Figure 2 Parts identification Note Leave a clearance of 4 100 mm if you do not open the top cover to se...

Страница 7: ...ble for input output signal lines and power line Unshielded cable can cause error due to noise Identification of the selector switches Figure 3 Selector switches Open close selector switch for input s...

Страница 8: ...w indicated on the valve body Do not install the product nearby a steam coil pressurized hot water coil or any high heat source High temperature radiation might cause malfunction of its actuator Insta...

Страница 9: ...ve seat may get damaged causing fluid leakage due to the sealing material jammed inside the valve Before activating the ACTIVAL fully open in 100 position the valve and flush the pipes with the ACTIVA...

Страница 10: ...he ACTIVAL before manually operating the ACTIVAL As shown in Fig 6 from the front of the ACTIVAL hold the joint using a tool such as a wrench and turn the joint slowly toward the set position Figure 6...

Страница 11: ...tion to mount onto the valve 4 A thermal insulation sheet is inserted between the yoke and the valve When changing the mounting positions reinsert the sheet and then fit the yoke into the new mounting...

Страница 12: ...ower supply and feedback signal and then correctly wire the product Incorrect wiring may result in PCB print circuit board burnout To prevent damage cover the terminals except when connecting disconne...

Страница 13: ...sult in electric shock Terminals connection 2 10 V DC input Figure 10 Terminals connection of Model VY514_J 4 20 mA DC input Figure 11 Terminals connection of Model VY519_J 1 Unscrew the setscrews 2 R...

Страница 14: ...isolated inside Isolation transformer is required for ACTIVAL Transformer without isolation may damage the ACTIVAL and other devices connected to ACTIVAL Model SDC35TD0 SDC36TD0 13 14 1 T1 2 T2 4 5 6...

Страница 15: ...ired for ACTIVAL Transformer without isolation may damage the ACTIVAL and other devices connected to ACTIVAL Model SDC35TC0 SDC36TC0 13 14 1 T1 2 T2 4 5 6 7 Figure 15 Connection example Two Model VY51...

Страница 16: ...Inspect the ACTIVAL according to Table 1 Manually open close the ACTIVAL at least once a month if it is left in inactive state for a long period Visually inspect the fluid leakage of the valve and th...

Страница 17: ...alve vibrates or produces an abnormal noise Primary pressure condition Differential pressure condition Adjust the mounting position and change the installation location The auxiliary switch does not o...

Страница 18: ...18 AB 7489 U This blank page was added for page layout purposes...

Страница 19: ...19 AB 7489 U This blank page was added for page layout purposes...

Страница 20: ...Kanagawa 251 8522 JAPAN AB 7489 U Rev 0 0 Mar 2018 This product complies with the following harmonised standards of the Electromagnetic Compatibility Directive EMCD and the Restriction of the use of...