![Azbil ACTIVAL FC200 Скачать руководство пользователя страница 7](http://html.mh-extra.com/html/azbil/actival-fc200/actival-fc200_specifications-and-instructions_3042535007.webp)
AB-6675
7
Valve and actuator (as a single unit) specifications
Item Specification
Environmental conditions
Rated operating condition
Limit operating condition
Transport/storage conditions
(packaged*
2
)
Ambient
temperature*
1
-20
C to 50
C -20
C to 60
C -20
C to 70
C
Ambient humidity
5 %RH to 95 %RH
Vibration
4.9
m/s
2
(10 Hz to 150 Hz)
4.9 m/s
2
to 9.8 m/s
2
(10 Hz to 150 Hz)
19.6 m/s
2
(10 Hz to 150 Hz)
Notes:
1 Do not allow the fluid to freeze.
2 Actuator shall be packed during transport.
Installation location
Indoor / outdoor (Keep away from direct sunlight.)
Note: Salt air, corrosive gas, flammable gas, and organic solvent must be avoided.
Mounting position
Refer to
■
“Installation,”
●
“Mounting position.”
Factory preset position
Port A 100 % (fully open)
Function
Function Specification
Data monitoring
Following items can be monitored/operated from the host system (savic-net FX) and Infilex GC/ Infilex GD.
Valve position setting, valve position measuring, sub-DO output, sub-DI monitoring
Note:
Above function is available in combination with Infilex GC/Infilex GD and savic-net FX.
Wire specifications
For details regarding specifications of SAnet communication line (24 V (
), GND (
), SAnet), refer to the Installation Manual of
SAnet for Intelligent Component Series (AB-6713).
Item Specification
Length
Contact input (sub-DI)
JIS CVV, JIS VCT, JIS IV, KPEV for low power
0.75 mm
2
, 0.9 mm
2
, 1.25 mm
2
, 2.0 mm
2
30 m
Contact output (sub-DO)
JIS CVV, JIS VCT, JIS IV, KPEV for low power
0.75 mm
2
, 0.9 mm
2
, 1.25 mm
2
, 2.0 mm
2
30 m
Note
KPEV: Wire standard provided by Furukawa Electric Co., Ltd.