AB-6675
16
IMPORTANT:
While the terminal cover is removed, do not touch the terminal block or allow anything to touch the terminal
block.
If the service pin switch is kept pressed for longer than 5 seconds, the mode will be switched and operation
error (data point trouble) will be occurred. In such a case, press the service pin switch again and keep it
pressed for longer than 10 seconds to go back to the normal mode.
Table 1. Basic address setting of this product and other Intelligent Component Series devices
Add. Device
Sub-DO
Sub-DI
1
Outdoor air damper
2
Exhaust air damper
3 Return
air
damper
4
Switch damper of total heat exchanger for outdoor air
5
Switch damper of total heat exchanger for exhaust air
6
Chilled/hot water valve / Chilled water valve
Filter alarm
7
Hot water valve (Chilled water valve*)
Humidifying ON/OFF
8 Humidifying
valve
D (13) Reserved
E (14) Reserved
F (15) Reserved
Notes:
1. For ‘chilled/hot water valve + chilled water valve’ application, set address 6 for chilled/hot water valve and 7 for chilled water valve.
2 Items in bold characters are the basic address to set for this product.
3 The above table is a basic setting example. Set address and use sub-I/O in response to system configuration, installation location, and
wiring best suitable for your application.