Phase 2:
The goal of the second phase is to remove any additional free water within the tank and also remove any large contaminants
and sludge. This phase will clean the fuel and should be a precursor to using the more expensive spin-on filters. It should
be noted that meeting required cleanliness codes is typically not possible with pre-filtering alone. Phase 2 is used to extend
the life of the spin-on filters, and remove the worst of the contaminants, before polishing with fine filters to meet the required
cleanliness.
1.
Keep the diverter valve in Bypass Mode (position #1).
2. Place the return line in the tank at the farthest point of the tank from the suction hose (secure discharge hose) (Figure
3.1).
Note: Never restrict the flow on the suction side of an MTC-X; e.g. by using a smaller ID hose or pipe or attaching the suction
hose to a fitting on the tank that has a smaller ID than the hose. This will lead to excessive pump load, noise, and ultimately
damage the pump.
3.
Ensure a pre-filter bag is equipped in the pre-filter vessel (Figure 3.2).
Phase 2 & Phase 3 setup for fuel polishing